Communication Driver Name: Genisys
Implementation DLL: T.ProtocolDriver.Genisys.dll
Protocol: Proprietary
Manufacturer: Genisys
PC Hardware Requirements: Serial Port
None
Master Mode: Not used in this driver
Slave Mode: The settings are configured as follows:
• Server Mode: True
• Accept Unsolicited: False
• Port: Port configured in the Master device
The station configuration has the following parameters:
Where:
• IP: IP Address
• Port: Port Number
• Slave ID: Slave ID in network
• Recall: Number of polls before a recall
• Secure Polls: Enable/Disable a CheckSum on the polls
Master Mode: All parameters must be configured
Slave Mode: Only IP and Slave ID parameters must be configured
The syntax for the Genisys communication point is:
When configuring the Write Address points, they must be in a Write Group since the communication always sends all 8 bits at once
To configure the WriteGroup AccessType, navigate to Edit > Devices > AccessTypes > Create New. Set a WriteTrigger to a Tag
After configuring the AccessType, go to Edit > Devices > Points. Set the Control points to the newly created AccessType
The status of the driver's execution can be observed through the diagnostic tools, which are:
• Trace window
• Property Watch
• Module Information
The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes.