Communication Driver Name: OmronCIP
Implementation DLL: T.ProtocolDriver. OmronCIP.dll
Protocol: OmronCIP (CIP over TCP/IP)
Interface: TCPIP
PLC types supported: NX-Series (tested with NX102-9020)
Manufacturer: OMRON
PC Hardware requirements: Ethernet board
Model: Set the PLC model. It can be:
Stations syntax: <IP>;<Port>;<Slot>
Where:
Name | Node | PrimaryStation | SecondaryStation | Description |
---|---|---|---|---|
Node1 | OmronCIP | 192.168.1.101;44818;0 |
The syntax for the ControlLogix communication points is: <Type>:<DeviceTagName>
Type | Read | Write | Size |
---|---|---|---|
BOOL | Yes | Yes | 1 bit |
SINT | Yes | Yes | 1 byte or 8 bits |
INT | Yes | Yes | 2 bytes or 16 bits |
DINT | Yes | Yes | 4 bytes or 32 bits |
REAL | Yes | Yes | 4 bytes or 32 bits IEEE Floating point |
REAL | Yes | Yes | 8 bytes or 64 bits IEEE Floating point |
STRING | Yes | Yes | n bytes |
The status of the driver's execution can be observed through the diagnostic tools, which are:
• Trace window
• Property Watch
• Module Information
The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol errors
Error Code | Description | Possible Solution |
---|---|---|
0 | Success | None |
-100 | Error Sending Message |
|
-101 | Error Sending and Waiting Message | |
-102 ... -105 | Error creating TCP/IP connection | |
-106 | Error Receiving Message | |
-112 | Timeout Start Message |
|
-113 | Timeout between Treated Chars | |
-114 | Timeout End Message | |
-115 | Timeout Connect | |
-200 | Protocol Error |
|
-201 | Invalid Protocol |
|
-202 | Invalid Station |
|
-204 | Invalid Message Sequence |
|
> 0 | CIP Error |
|
The following error codes are in decimal.
Error Code | Description |
---|---|
1 | Connection Failure |
2 | Insufficient resources |
3 | Value invalid |
4 | IOI could not be deciphered or tag does not exist |
5 | Unknown destination |
6 | Requested Data would not fit in the response packet |
7 | Loss of connection |
8 | Unsupported service |
9 | Error in data segment or invalid attribute value |
10 | Attribute list error |
11 | State already exists |
12 | Object model conflict |
13 | Object already exists |
14 | Attribute not settable |
15 | Permission denied |
16 | Device state conflict |
17 | Reply will not fit |
18 | Fragment primitive |
19 | Insufficient command data / parameters specified to execute service |
20 | Attribute not supported |
21 | Too much data specified |
26 | Bridge request too large |
27 | Bridge response too large |
28 | Attribute list shortage |
29 | Invalid attribute list |
30 | Embedded service error |
31 | Failure during connection |
34 | Invalid reply received |
37 | Key segment error |
38 | Number of IOI words specified does not match IOI word count |
39 | Unexpected attribute in list |
It is very important to enable the TraceWindow messages. Invalid addresses can cause all the communication blocks with the PLC to fail. When the Device is enabled in the settings, the TraceWindow tool will display the first invalid address found on the block.
In order to have a quick view of the many communication blocks, open the ModuleInformation, navigate on the tree to find OmronCIP and them select the Read Groups. Looking at the number and success and fail communication counters, you can easily identify if there is a block with error and then use the TraceWindow to locate the wrong address.