Page Tree
Other Releases
Communication Driver Name: Siemens
Current Version: 2.2.2.0
Implementation DLL: T.ProtocolDriver. Siemens.dll
Third Party Libraries: AGL4DotNET.dll, AGLink40.dll, and AGLink40_x64.dll
Interface: TCPIP
PLC types supported: Devices S7 300/400/1200/1500
Manufacturer: Siemens
PC Hardware requirements: Ethernet board
Device Number: Used for connection when there is more than one PLC in the network
PLC Number: Slave PLC number
Station syntax: <IP Address>;<Rack>;<Slot>;<S7 Family>
Where:
300/400: Support for PLC Siemens S7-300 and S7-400 Series
1200: Support for PLC Siemens S7-1200 and S7-1500 Series
The syntax for the Siemens communication points is: <Type>:<Format><Address>.<Bit or String Length>
For DataBlock type: DB<DB Group>:<Format><Address>.<Bit or String Length>
Where:
The status of the driver execution can be observed through the diagnostic tools, which are:
• Trace window
• Property Watch
• Module Information
The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes.