This document has only the specific information about the device connection settings and its address syntax.

Refer to the User Guide for more information on the Device Module.

On this page:


Summary

Communication Driver Information

Driver name

Siemens

Assembly Name

T.ProtocolDriver.Siemens

Assembly Version

2.2.2.0

Available for Linux

False

Devices supported 

S7 300/400

Third-party libraries

AGL4DotNET.dll, AGLink40.dll and AGLink40_x64.dll.

Manufacturer

Siemens

Protocol

Proprietary over TCP/IP

PC Requirements

Ethernet port


Channels Configuration

Protocol Options

  • Device Number: Used for connection when there is more than one PLC in the network.
  • PLC Number: Slave PLC number



Nodes Configuration

Station Configuration

Station syntax: <IP  Address> ; <Rack>; <Slot>

Where :

  • <IP Address>: IP address of the slave device in the Siemens network
  •  <Rack>: Rack of the device
  •  <Slot>: Slot of the device



Points Configuration

Address

The syntax for the Siemens communication points is: <Type>:<Format><Address>.< Bit or String Length >

For DataBlock type: DB<DB Group>:<Format><Address>.<Bit or String Length>

Where:

  • <Type>  is the register type. Valid values are: 
    • M=Flags
    • T=Timers
    • C=Counters
    • I=Inputs
    • Q=Outputs
    • DB=Data Blocks.
  • <DB Group> is the group number of the configured Data Block type.
  • <Address> is the device address.
  • <Format>  is the format to treat the value from or to the device. Valid values are:
    • B=Byte
    • W=Word
    • DW=Dword
    • F=Float
    • ST=String
  • <Bit or String Length> is the bit number. This parameter is optional. If you use the String type, it represents the String length.


Error Code Reference

HexDecimal (signed)Description
0x000000000No error
0x000000011No error, job still in process
0xFFF00000-1048576Function not implemented
0xFFF00001-1048575Parameter error when calling function
0xFFF00002-1048574Invalid device number
0xFFF00003-1048573Invalid PLC number
0xFFF00004-1048572Invalid parameter type
0xFFF00005-1048571Insufficient memory
0xFFF00006-1048570Device already opened
0xFFF00007-1048569Device not opened
0xFFF00008-1048568Job already removed
0xFFF00009-1048567Invalid job number
0xFFF0000A-1048566Function not supported
0xFFF0000B-1048565Adapter not initialized
0xFFF0000C-1048564No free connections available
0xFFF0000D-1048563Device not configured or not supported
0xFFF0000E-1048562Hardware not found
0xFFF0000F-1048561Error when reading parameters
0xFFF00010-1048560Error when writing parameters
0xFFF00011-1048559Demo period expired
0xFFF00012-1048558Wrong character in text. Conversion not possible
0xFFF00013-1048557Buffer is not long enough
0xFFF00014-1048556File not found
0xFFF00015-1048555Error when calling configuration program
0xFFF00016-1048554Error when loading DLL dynamically
0xFFF00017-1048553Could not create file
0xFFF50000-720896No free job buffer available
0xFFF50001-720895Invalid packet
0xFFF50002-720894No connection to PLC
0xFFF50003-720893Connection closed
0xFFF50004-720892Timeout
0xFFF50005-720891Invalid context
0xFFF50006-720890PLC memory error
0xFFF50007-720889Invalid operating state
0xFFF50008-720888Invalid address on PLC
0xFFF50009-720887Invalid mode
0xFFF5000A-720886No data available e.g. DB is missing
0xFFF5000B-720885Priority class associated to OB does not exist
0xFFF5000C-720884Empty blocklist
0xFFF5000D-720883Block size error
0xFFF5000E-720882Invalid block number
0xFFF5000F-720881Protection level of function not sufficient
0xFFF50010-720880Unknown SSL-ID (e.g. access to CP instead of PLC)
0xFFF50011-720879Unknown SSL-index (e.g. access to CP instead of PLC)
0xFFF50012-720878Information currently not ascertainable
0xFFF50013-720877Unknown error message from PLC (please report!)
0xFFF50014-720876Hardware error e.g. not available periphery
0xFFF50015-720875Object access not allowed
0xFFF50016-720874Context not supported
0xFFF50017-720873Type (data type) not supported
0xFFF50018-720872Internal error, please report
0xFFF50019-720871Error rebooting PLC
0xFFF5001A-720870Error restarting PLC
0xFFF5001B-720869Connection end received
0xFFF5001C-720868PLC not found
0xFFF5001D-720867Too many data for this version of ACCON-AGLink
0xFFF5001E-720866PLC does not support this function
0xFFF5001F-720865Wrong Password
0xFFF50020-720864Connection already legitimated
0xFFF50021-720863Legitimation already released
0xFFF50022-720862Password not neccessary
0xFFF50023-720861At least one variable address invalid
0xFFF50024-720860Job does not exist
0xFFF50025-720859Invalid job state
0xFFF50026-720858Invalid cycle time
0xFFF50027-720857No more cyclic job possible
0xFFF50028-720856Function not posible for this job (invalid state)
0xFFF50029-720855Function abort (overload)
0xFFF5002A-720854No data for this variable
0xFFF5002B-720853Wrong time format
0xFFF5002C-720852Unknown PI name
0xFFF5002D-720851File transfer canceled by NCK
0xFFF5002E-720850Response too large for PDU size
0xFFF5002F-720849No H-PLC found
0xFFF50030-720848Data not changed
0xFFF30000-852968Error when reading device information
0xFFF30001-852967Error when reading bus parameters
0xFFF30002-852966Error when writing bus parameters
0xFFF30003-852965No resources available on device
0xFFF30004-852964Invalid device
0xFFF30005-852963Adapter not found
0xFFF30006-852962Needed device driver not found
0xFFF20000-917504The desired adapter address already exists
0xFFF20001-917503Invalid HSA (smaller than biggest active participant)
0xFFF20002-917502Adapter is not in the logical ring
0xFFF20004-917500Received package has wrong content
0xFFF20006-917498Unknown error number from adapter
0xFFF20007-917497Unknown error number from device driver
0xFFF20008-917496Communications adapter has been removed
0xFFF20009-917495Modem has been removed
0xFFF2000A-917494No directly connected PLC found
0xFFF20313-916717Invalid speed on MPI bus
0xFFF20314-916716Address is bigger than HSA
0xFFF20315-916715The desired adapter address already exists
0xFFF2031A-916710No other active bus participants found
0xFFF2031C-916708Bus is jammed
0xFFF2031D-916707Bus is jammed
0xFFF2031E-916706Automatic detection of bus profile doesn't work, missing bus parameter telegram
0xFFF20337-916681Legitimation missing
0xFFF10000-983040COM-Port already used
0xFFF10001-983039Modem not found
0xFFF10002-983038Modem not onhook
0xFFF10003-983037Modem not offhook
0xFFF10004-983036Error in basic initialisation
0xFFF10005-983035Error in Initstring 1
0xFFF10006-983034Error in Initstring 2
0xFFF10007-983033Error in Initstring 3
0xFFF10008-983032Error in Initstring 4
0xFFF10009-983031Error in dialtype sequence
0xFFF1000A-983030Error in dialtone sequence
0xFFF1000B-983029Error in autoanswer sequence
0xFFF1000C-983028Modem has been removed
0xFFF1000D-983027Connection could not be established
0xFFF1000E-983026Login denied. Unknown user.
0xFFF1000F-983025Login denied. Wrong password.
0xFFF10010-983024Login denied. Callback number defined in adapter.
0xFFF10011-983023Error while dialing
0xFFF80000-524288Function not allowed
0xFFF80001-524287Invalid project handle
0xFFF80002-524286Error opening project
0xFFF80003-524285Error creating program instance of project
0xFFF80004-524284Error closing project
0xFFF80005-524283No resp. no more programs found
0xFFF80006-524282Program not found
0xFFF80007-524281At least one of the specified parameters is invalid
0xFFF80008-524280Runtime has expired (demo version)
0xFFF8000A-524278No resp. invalid data specified
0xFFF8000B-524277The program selected has no symbol table
0xFFF8000C-524276Symbol table already opened
0xFFF8000D-524275No resp. no more symbol entry found
0xFFF8000E-524274Error reading symbol entry
0xFFF8000F-524273Symbol not found
0xFFF80010-524272Operand not found
0xFFF80011-524271Invalid symbol
0xFFF80012-524270Invalid operand
0xFFF80013-524269Invalid filter string
0xFFF80014-524268Data block (DB) not present
0xFFF80015-524267Error reading DB block data
0xFFF80016-524266Error parsing DB block data
0xFFF80017-524265An opened DB is already present
0xFFF80018-524264No opened DB present
0xFFF80019-524263No resp. no more DB component found
0xFFF8001A-524262Specified DB component not found
0xFFF8001B-524261Specified DB component is invalid
0xFFF8001C-524260Specified DB component not matching
0xFFF8001E-524258Invalid constant
0xFFF8001F-524257Invalid constant size or format
0xFFF80020-524256Object type initialization failed
0xFFF80021-524255Invalid version of message configuration
0xFFF80022-524254Error opening message configuration
0xFFF80023-524253Error closing message configuration
0xFFF80024-524252No resp. no more message entry found
0xFFF80025-524251No resp. no more language found
0xFFF80026-524250Database access error
0xFFF80027-524249Invalid signal number
0xFFF80028-524248Invalid add. value specification
0xFFF80029-524247Add. value number invalid
0xFFF8002A-524246Element type of add. value invalid
0xFFF8002B-524245Add. value data length invalid
0xFFF8002C-524244Format specification missing
0xFFF8002D-524243Format specification invalid
0xFFF8002E-524242No resp. no more text library found
0xFFF8002F-524241No resp. no more text library entry found

Driver Revision History

Siemens Revision History

Version 

Notes

2.2.2.0

Initial release on new documentation standards.