Page properties | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||
|
Devices compatible with Mitsubishi FX3U
- Name: MitsubishiFXSerial
- Version:
This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module or on UNS TagProvider Connections.
On this page:
Table of Contents | ||||||
---|---|---|---|---|---|---|
|
Summary
Communication Driver Information
Driver name
MitsubishiFXSerial
Assembly Name
T.ProtocolDriver.MitsubishiFXSerial
Assembly Version
- 1.0.1.0
- Protocol: ADS
- Interface: Standard Serial Port
- Runtime: Multiplatform
- Configuration:
- Devices / Protocols
On this page:
Table of Contents | ||||||
---|---|---|---|---|---|---|
|
Overview
Communication with devices compatible with Mitsubishi FX3U
Available for Linux
False
Devices supported
FX3U
Manufacturer
Mitsubishi
Protocol
Proprietary
PC Requirements
Supported Operands
Operand | Read | Write | Data Type | Address size |
D - Data register | Yes | Yes | Word | 2 bytes |
TN – Timer Current value | Yes | Yes | Word | 2 bytes |
TS – Timer Contact | Yes | No | Bit | 1 bit |
CN – Counter Current value | Yes | Yes | Word | 2 bytes |
CS – Counter Contact | Yes | No | Bit | 1 bit |
X - Input relay | Yes | No | Bit | 1 bit |
Y - Output relay | Yes | Yes | Bit | 1 bit |
M - Internal relay | Yes | Yes | Bit | 1 bit |
S0 - Annunciator | Yes | Yes | Bit | 1 bit |
Channels Configuration
Protocol Options
Maximum size of blocks: Defines the maximum of addresses in a read block.
Protocol Options
- Com – Define the Port of communication
- Baud Rate – Define the rate at which information is transferred in a communication channel.
- Databits – Define the number of data bits in each character
- Parity – Define the method of detecting errors in transmission.
- Stop bits – Define the stop bits.
- DTR – Define a control signal in RS-232 serial communication.
- RTS – Define the Request to Send
- CTS – Define the Clear to Send
- CtsWait – Time in milliseconds
Nodes Configuration
Primary Station
- SlaveID: The default is 1.
Points Configuration
The syntax for the Mitsubishi FX Serial communication points is: <Operand> <Address>
Where :
- <Operand>: Represents the Device Memory :
- <Address>: Address number
Operand |
---|
D - Data register |
TN – Timer Current value |
TS – Timer Contact |
CN – Counter Current value |
CS – Counter Contact |
X - Input relay |
Y - Output relay |
M - Internal relay |
S0 - Annunciator |
Note: The Y Operand is an Octal Numeral System.
Driver Revision History
MitsubishiFX_Serial Revision History | |
---|---|
Version | Notes |
1.0.1.0 | Initial release on new documentation standards |
In this section:
Page Tree | ||||
---|---|---|---|---|
|