Page properties | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||
|
Mitsubishi FX Series and compatible
- Name: MelsecFX
- Version: 1.0.1.0
- Protocol: Melsec Q 1E frame
- Interface: TCP/IP
- Runtime: Multiplatform
- Configuration:
- Devices / Protocols
This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module.On this page:
Table of Contents | |
---|---|
|
|
Overview
MelsecFX communication driver implements communication with Mitsubishi FX Series PLCs using Melsec Q 1E frame. It operates as a Master on TCP/IP networks. The communication blocks are dynamically created according to the pooling cycle defined on the AccessType for each point.
Communication Driver InformationDriver name
MelsecFX
Assembly Name
T.ProtocolDriver.MelsecFX
Assembly Version
1.0
Available for Linux
False
Devices supported
Mitsubishi FX Series PLCs and compatibles (MelsecQ 1E Frame)
Manufacturer
Mitsubishi
Protocol
Melsec Q 1E frame
Interface
TCP/IP
Multi-threading
User defined
Max number of nodes
User defined
PC Requirements
Ethernet port
Supported Operands
Operand | Read | Write | Data Type | Address size |
---|---|---|---|---|
D - Data register | Yes | Yes | Short | 2 bytes |
W - Link register | Yes | Yes | Short | 2 bytes |
R - File register | Yes | Yes | Short | 2 bytes |
TN – Timer Current value | Yes | Yes | Short | 2 bytes |
TS – Timer Contact | Yes | Yes | Bit | 1 bit |
TC – Timer Coil | Yes | Yes | Bit | 1 bit |
CN – Counter Current value | Yes | Yes | Short | 2 bytes |
CS – Counter Contact | Yes | Yes | Bit | 1 bit |
CC – Counter Coil | Yes | Yes | Bit | 1 bit |
X - Input relay | Yes | Yes | Bit | 1 bit |
Y - Output relay | Yes | Yes | Bit | 1 bit |
M - Internal relay | Yes | Yes | Bit | 1 bit |
B - Link relay | Yes | Yes | Bit | 1 bit |
F - Annunciator | Yes | Yes | Bit | 1 bit |
Channel Configuration
Protocol Options
- Maximum size of blocks: Defines the maximum of addresses in a read block.
Settings
TCP/IP:
- NodeConnections: Defines the maximum number of parallel requests that will be sent to each node (asynchronous communication)
Node Configuration
Station Configuration
TCP/IP:
- Station syntax: <IP address> ; <Port number>
Where :
- <IP address>: IP address of the slave device in the modbus network
- <Port number>: TCP port where the slave device is listening (default is 44818)
E.g.: 192.168.1.1 ; 5551
Points Configuration
The syntax for the MelsecFX communication points is: <Operand> <Address>
Where :
- <Operand>: Represents the Device Memory :
- <Address>: Address number
Operand |
---|
D - Data register |
W - Link register |
R - File register |
TN – Timer Current value |
TS – Timer Contact |
TC – Timer Coil |
CN – Counter Current value |
CS – Counter Contact |
CC – Counter Coil |
X - Input relay |
Y - Output relay |
M - Internal relay |
B - Link relay |
F - Annunciator |
Driver Revision History
MelsecFX Revision History | |
---|---|
Version | Notes |
1.0 | Initial release on new documentation standards. |
In this section...
Page Tree | ||||
---|---|---|---|---|
|