PLC Allen-Bradley MicroLogix 1761 - NET-ENI
- Name: ABENI
- Version
- 1.
- 9.
- 1.1
Multiplatform runtime
Modules: Device
Manufacturer: Allen-Bradley / Rockwell- Protocol: AB_ENI
- Interface: TCP/IP
- Runtime: .NET 2.0 (Multiplatform)
- Configuration:
- Devices / Protocols
On This Page:
Table of Contents | ||||||
---|---|---|---|---|---|---|
|
Module Configuration
This document has only information about the device connection settings and its address syntax.
For further Information, see:
Channels Configuration
Protocol Options
This configuration is not supported for this Driver.
Nodes Configuration
Primary Station
Station syntax: <IP > ; <Port >
Where:
<IP> = IP address of the slave device in the AB network
<Port> = TCP port where the slave device is listening (default is 44818)
E.g.: 192.168.1.1 ; 44818
Points Configuration
Address
The syntax for the AB ENI communication points are:
- <FileType><FileNumber>:<ElementNumber><Parameter>
Where <FileType> indicates the memory area, the valid values are:
- N, for Integer
- B, for digital
- F, for real
- S, for statur
AB ENI Address Types | ||||
---|---|---|---|---|
Type | Read | Write | Data Type | Address size |
N | Yes | Yes | Word | 2 bytes |
B | Yes | Yes | Word | 2 bytes |
F | Yes | Yes | Single | 4 bytes |
S | Yes | Yes | Word | 2 bytes |
<FileNumber> indicates the data address for the chosen file
<ElementNumber> indicates the address from the specific file which will read and/or write from PLC.
<Parameter> indicates the parameter that composes the ElementNumber.
E.g.:
- F8:0
- N7:1
- B3:10/1