Page properties
hiddentrue
idconnector-metadata


Property

Value

Sector

Factory-Floor Interfaces

Group

Field Devices

Connector

TTS08 SD50 Server

Name

TTS08



TTS08 family devices

  • Name: TTS08
  • Version: 1.1.0.1
  • Protocol: Proprietary
  • Interface: TCP/IP
  • Runtime: .NET 2.0 (Multiplatform)
  • Configuration:
    • Devices / Protocols

On This Page

This document has only specific information about the device connection settings and its address syntax. 

Refer to the User Guide for more information on the Device Module.

On this page

:

Table of Contents
maxLevel

3

2
minLevel2
stylenone

Summary

Overview

Communication Driver Information

Driver name

TTS08

Assembly Name

T.ProtocolDriver.TTS08

Assembly Version

1.1.0.1

Available for Linux

False

Devices supported 

TTS08 family devices

Manufacturer

McCoy Global

Protocol

The SD50 is a TCPIP server that supplies a binary encoded sensor data stream on port 9876 and listens for parameter tare commands on port 9976

Interface

TCP/IP

PC Requirements

Ethernet port




Channels

Channel Configuration

Protocol Options

Not used in this driver.

Settings

  • AcceptUnsolicited must be checked.
Nodes



Node Configuration

Station Configuration

Station syntax: <IP> ; <Port>

 Where:

  • <IP>: SD50 IP Address
  • <Port>:  9876 must be set to receive the data stream.



Points Configuration

Address

The syntax for the TTS08 communication points is: <SensorTxId>:<ItemID>

Where:

  • <SensorTxId>:  Sensor TxId in Hexa.  
  • <ItemID>: Specific item to be read, such as:
    • Battery
    • Pressure
    • Tension
    • Torque
    • Temperature
    • X_Axis_Acceleration
    • Y_Axis_Acceleration
    • Z_Axis_Acceleration
    • RPM



Driver Revision History

TTS08 Revision History

Version 

Notes

1.1.0.1

Initial release on new documentation standards.