Page properties | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||
|
Emerson WirelessHart HartIP devices
- Name: WirelessHart
- Version: 2.0.0.8
- Protocol: HartIP
- Interface:TCP/IP
- Runtime: Multiplatform
- Configuration:
- Devices / Protocols
On This Page:
Table of Contents | ||||||
---|---|---|---|---|---|---|
|
Module Configuration
This document has only information about the device connection settings and its address syntax.
For further Information, see:
- Devices - Field Communications Module (Concept)
- Devices Module (Reference)
Device Information
Manufacturer: Emerson
Hart Supported Commands | ||
---|---|---|
Command | Read | Write |
Command 0 – Read Unique Identifier | Yes | - |
Command 3 – Read Dynamic Variables and Loop Current | Yes | - |
Command 9 – Read Device Variables and Status | Yes | - |
Command 13 – Read Tag, Descriptor and Date | Yes | - |
Command 20 – Read Long Tag | Yes | - |
Command 38 – Reset Configuration Changed Flag | Yes | - |
Command 48 – Read Device Additional Status | Yes | - |
Command 50 – Read Dynamic Variable Assignments | Yes | - |
Command 74 – Read I/O System Capabilities | Yes | - |
Command 84 – Read Sub-Device Identity Summary | Yes | - |
Command 101 – Read Sub-device to Burst Message Map | Yes | - |
Command 105 – Read Burst Mode Configuration | Yes | - |
Command 178 – Publish Dynamic Data | Yes | - |
Channels Configuration
Protocol Options
Not used in this driver.
Node Configuration
Station Configuration
Station syntax: <IP address> ; <Port number>
Where:
- <IP address>:IP address of the Hart gateway
- <Port number>: TCP port where the gateway is listening (default is 5094)
E.g.: 192.168.0.107;5094
Point Configuration
The syntax for the communication points is: <DeviceTag>.<Command>: <Parameter>
E.g.: Acoustic708-050001.178:PVDeviceVariableValue
Where :
- <DeviceTag>: It will be brought from Hart gateway.
- <Command>: Hart Commands. See the table below for the availables command.
Command | Description |
0 | Read Unique Identifier |
3 | Read Dynamic Variables and Loop Current |
9 | Read Device Variables and Status |
13 | Read Tag, Descriptor and Date |
20 | Read Long Tag |
38 | Reset Configuration Changed Flag |
48 | Read Device Additional Status |
50 | Read Dynamic Variable Assignments |
74 | Read I/O System Capabilities |
84 | Read Sub-Device Identity Summary |
101 | Read Sub-device to Burst Message Map |
105 | Read Burst Mode Configuration |
178 | Publish Dynamic Data |
- <Parameter>: It is a number that represent each parameter of the command response. See the tables below:
Command 0 |
Parameters |
Expansion Code |
Expanded Device Type Code |
Request Preambles |
Universal Revision Level |
Transmitter Revision Level |
Software Revision |
Hardware Revision Level / Physical Signing Code |
Flags |
Device Identification Code |
Minimum# Response Preambles |
Max# of Device Variable |
Configuration Change Counter |
Extended Field Device Status |
Manufacture Identification Code |
Private Label Distributor |
Device Profile |
Command 3 |
Parameters |
PV Loop Current (many wireless devices return NaN, no analog output) |
PV Units Code |
PV |
SV Units Code |
SV |
TV Units Code |
TV |
QV Units Code |
QV |
Command 9 |
Parameters |
Slot 0: Device Variable Code |
Slot 0: Device Variable Classification |
Slot 0: Device Variable Units Code |
Slot 0: Device Variable Value |
Slot 0: Device Variable Status |
Slot 1: Device Variable Code |
Slot 1: Device Variable Classification |
Slot 1: Device Variable Units Code |
Slot 1: Device Variable Value |
Slot 1: Device Variable Status |
Slot 2: Device Variable Code |
Slot 2: Device Variable Classification |
Slot 2: Device Variable Units Code |
Slot 2: Device Variable Value |
Slot 2: Device Variable Status |
Slot 3: Device Variable Code |
Slot 3: Device Variable Classification |
Slot 3: Device Variable Units Code |
Slot 3: Device Variable Value |
Slot 3: Device Variable Status |
Slot 4: Device Variable Code |
Slot 4: Device Variable Classification |
Slot 4: Device Variable Units Code |
Slot 4: Device Variable Value |
Slot 4: Device Variable Status |
Slot 5: Device Variable Code |
Slot 5: Device Variable Classification |
Slot 5: Device Variable Units Code |
Slot 5: Device Variable Value |
Slot 5: Device Variable Status |
Slot 6: Device Variable Code |
Slot 6: Device Variable Classification |
Slot 6: Device Variable Units Code |
Slot 6: Device Variable Value |
Slot 6: Device Variable Status |
Slot 7: Device Variable Code |
Slot 7: Device Variable Classification |
Slot 7: Device Variable Units Code |
Slot 7: Device Variable Value |
Slot 7: Device Variable Status |
Slot 0: Time Stamp (units of 1/32 of a mS or 0.00003125 seconds or 31.25 μS) |
Command 13 |
Parameters |
Tag |
Descriptor |
Day |
Month |
Year since 1900 |
Command 20 |
Parameter |
Long Tag |
Command 38 |
Parameter |
Configuration Change Counter (previously read value) |
Command 48 |
Parameters |
Transmitter Status 0 |
Transmitter Status 1 |
Transmitter Status 2 |
Transmitter Status 3 |
Transmitter Status 4 |
Transmitter Status 5 |
Extended Device Status |
Device Operating Mode |
Standardize Status 0 |
Standardize Status 1 |
Analog Channel Saturated |
Standardize Status 2 |
Standardize Status 3 |
Command 50 |
Parameters |
Device Variable mapped to PV |
Device Variable mapped to SV |
Device Variable mapped to TV |
Device Variable mapped to QV |
Command 74 |
Parameters |
Maximum Number of I/O Cards (must be ≥1) |
Maximum Number of Channels per I/O Card (must be ≥1) |
Maximum Number of Sub-Devices per Channel (must be ≥1) |
Number of devices detected (the count includes the I/O system itself) |
Maximum number of delayed responses supported by the I/O system. (must be ≥ 2) |
Master mode for communication on channels. 1 = Primary Master (default) |
Retry count to use when sending commands to a sub-device. (Range 2 ≤ value ≤ 5) |
Command 84 |
Parameters |
Sub-device index |
I/O Card |
Channel |
Manufacturer Id |
Expanded Device Type Code |
Device Id |
Universal Command Revision |
Long Tag |
Device Revision |
Device Profile |
Private Label Distributor |
Command 101 |
Parameters |
Burst Message |
Sub-device Index (index 0 indicates the I/O System itself) |
Command 105 |
Parameters |
Burst Mode Control Code |
Command Number (usually 31 for HART 7 devices, see Extended Command Number) |
Device Variable Code Assigned to Slot 0 |
Device Variable Code Assigned to Slot 1 |
Device Variable Code Assigned to Slot 2 |
Device Variable Code Assigned to Slot 3 |
Device Variable Code Assigned to Slot 4 |
Device Variable Code Assigned to Slot 5 |
Device Variable Code Assigned to Slot 6 |
Device Variable Code Assigned to Slot 7 |
Burst Message |
Maximum number of burst messages supported by this device |
Extended Command Number |
Update Time (burst period) |
Maximum Update Time |
Burst Trigger Mode |
Device Variable Classification |
Trigger Units Code |
Trigger Level |
Command 178 |
Parameters |
Number of command in the structure (typically 2 for cmd 9 and cmd 48) |
Command Number 1 (typically 9) |
Command Number 1 Byte Count (varies depending on command payload) |
Command Number 1 Response code |
Extended Device Status |
PV Device Variable Code |
PV Device Variable Classification |
PV Device Variable Units Code |
PV Device Variable Value |
PV Device Variable Status |
SV Device Variable Code |
SV Device Variable Classification |
SV Device Variable Units Code |
SV Device Variable Value |
SV Device Variable Status |
TV Device Variable Code |
TV Device Variable Classification |
TV Device Variable Units Code |
TV Device Variable Value |
TV Device Variable Status |
QV Device Variable Code |
QV Device Variable Classification |
QV Device Variable Units Code |
QV Device Variable Value |
QV Device Variable Status |
PV % Range Device Variable Code (variable code = 244 typically) |
PV % Range Device Variable Classification |
PV % Range Device Variable Units Code (typically 57 = %) |
PV % Range Device Variable Value |
PV % Range Device Variable Status |
PV Loop Current Device Variable Code (variable code = 245 typically) |
PV Loop Current Device Variable Classification |
PV Loop Current Device Variable Units Code (typically 39 = mA) |
PV Loop Current Device Variable Value |
PV Loop Current Device Variable Status |
PV Time Stamp |
Command Number 2 (typically 48) |
Command Number 2 Byte Count (varies depending on command payload) |
Command Number 2 Response code |
Transmitter status byte 0 |
Transmitter status byte 1 |
Transmitter status byte 2 |
Transmitter status byte 3 |
Transmitter status byte 4 |
Transmitter status byte 5 |
Extended Device Status |
Device Operating Mode |
Standardized Status 0 |
Standardized Status 1 |
Analog Channel Saturated (usually 0) |
Standardized Status 2 |
Standardized Status 3 |
Driver Revision History
WirelessHart Revision History | |
---|---|
Version | Notes |
2.0.0.8 | Initial release on new documentation standards. |
In this section...
Page Tree | ||||
---|---|---|---|---|
|