Control automation professionals with experience in PLCs, HMIs, and SCADA systems focusing on reliable control, operator interfacesUI, and field device integration.

...

  • Connect and configure industrial devices
  • Design effective operator interfacesUI
  • Implement alarm management strategies
  • Create control logic and calculations
  • Build trending and historical displays

...

Day 5: Alarm Configuration

Alarm Priority Matrix

Priority

Range

Color

Response Time

Consequence

Critical

1-200

Red

Immediate

Safety shutdown

High

201-400

Orange

10 minutes

Process upset

Medium

401-600

Yellow

30 minutes

Efficiency loss

Low

601-999

Blue

Next shift

Maintenance required

Lab: Configure Process Alarms

Tank Level Alarm Configuration:

Alarm

Trigger

Priority

Deadband

Delay On

Delay Off

HiHi

95%

250

2%

5 sec

3 sec

Hi

85%

400

2%

5 sec

3 sec

Lo

15%

400

2%

5 sec

3 sec

LoLo

5%

250

2%

5 sec

3 sec

Week 2: Advanced Topics

Day 1-2: Control Logic Implementation

...

Day 3-4: Trending Configuration

Trend Setup Parameters

Component

Configuration

Time Axis

Real-time (last hour), Historical (date range), Resolution (1 sec - 1 day)

Y-Axes

Primary (0-100%), Secondary (0-150°F), Auto-scale option

Pens

Multiple process values with distinct colors

Exercise: Build Trending Display

...

Day 5: Performance Optimization

Optimization Guidelines

Area

Technique

Benefit

Scan Rates

Match process dynamics

Reduce network load

Display Updates

Limit animations

Improve client performance

Alarm Deadbands

Prevent chattering

Reduce alarm floods

Script Efficiency

Avoid loops in expressions

Lower CPU usage

Standard Component Library

...

Communication Quick Reference

PLC Type

Protocol

Default Settings

Allen-Bradley

EtherNet/IP

Slot 0, RPI 100ms

Siemens

S7 TCP

Rack 0, Slot 2

Modbus Devices

Modbus TCP

Port 502, Unit ID 1

Schneider

Modbus TCP

Port 502, Holdings

Omron

FINS

Port 9600, Node 1

Troubleshooting Guide

Issue

Check

Solution

PLC won't connect

IP address, subnet

Verify network settings

Tags not updating

Point mapping

Check addresses match PLC

Alarms flooding

Deadband, delays

Adjust alarm settings

HMI slow

Graphics complexity

Simplify animations

Trends gaps

Historian settings

Check storage configuration