Alarms & Audit-Trail Tutorial teaches you to:

  • Create alarm groups and items
  • Configure alarm conditions
  • Set up notifications
  • Enable audit trail for FDA 21 CFR Part 11 compliance

Prerequisites:

In this page:

Table of Contents
maxLevel2
minLevel2
indent10px
excludeSteps
stylenone



Tutorial | Concept | How-to Guide | Reference


Create Alarm Groups

  1. Navigate to Alarms → Groups
  2. Edit the groups:
CriticalWarning
  • Priority: 1
  • Acknowledgment: Required
  • Priority: 3
  • Acknowledgment: not required 



Define Alarm Items

  1. Go to Alarms → Items
  2. Create alarms:
High TemperatureLow Level
  • Tag: Tank1_Temperature
  • Group: Critical
  • Condition: Greater than
  • Limit: 85
  • Message: Tank 1 temperature exceeds limit
  • Tag: Tank1_Level
  • Group: Warning
  • Condition: Less than
  • Limit: 10
  • Message: Tank 1 level low

Configure Deviation Alarms

For rate-of-change monitoring:

  • Name: Pressure_Deviation
  • Type: Deviation
  • Tag: Line_Pressure
  • Setpoint Tag: Pressure_Setpoint
  • Deviation: ±10
  • Time: 60 seconds

Configure Audit Trail

  • Go to Alarms → Audit Trail
  • Enable logging:
    • Login/Logout: Yes
    • Tag Changes: Yes
    • Alarm Acknowledgments: Yes
    • Configuration Changes: Yes
Set storage:
  • Database: SQL Server
  • Table: AuditTrail
  • Retention: 365 days
  • Alarm Summary Display

    • Create operator display:
      • Displays → New
      • Add AlarmViewer control
    • Configure:
      • Show: Active alarms
      • Columns: Time, Area, Message, Value
    Filter
      • ilter: By area or priority
      • Allow: Acknowledge, silence

    Test Alarms

    1. Start Runtime
    2. Open Alarms → Online
    3. Force tag values to trigger alarms
    4. Verify:
      • Alarm appears in list
      • Color coding correct
      • Sound plays
      • Email sent

    In this section...

    Page Tree
    root@parent
    spaces93DRAF