Page properties | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||
|
Devices compatible with Mitsubishi FX3USNP protocol.
Table of Contents | ||||||
---|---|---|---|---|---|---|
|
Communication with devices compatible with Mitsubishi FX3U
SNP protocol.
Communication Driver Information | |
---|---|
Driver name | Snp |
Assembly Name | T.ProtocolDriver.Snp |
Assembly Version | 1.0 |
Available for Linux | False |
PLC types supported | GE Fanuc PLCs - 90/30 and 90/70 Series, PACSystem and VersaMax. |
Interface | Serial and MultiSerial |
SNP (Series Ninety Protocol) was created by GE Fanuc Automation (GE + Fanuc). Later the brand became GE Intelligent Platforms, and today the PLC line (PACSystems/VersaMax) is with Emerson.
AI | Analog Input |
AQ | Analog Output |
G | Discrete Global Memory |
I | Discrete Input |
Q | Discrete Output |
T | Output (Temporary) Coils |
M | Internal Coils |
S | System Status |
R | Register Memory |
Operand
Read
Write
Data Type
Address size
D - Data register
Yes
Yes
Word
2 bytes
TN – Timer Current value
Yes
Yes
Word
2 bytes
TS – Timer Contact
Yes
No
Bit
1 bit
CN – Counter Current value
Yes
Yes
Word
2 bytes
CS – Counter Contact
Yes
No
Bit
1 bit
X - Input relay
Yes
No
Bit
1 bit
Y - Output relay
Yes
Yes
Bit
1 bit
M - Internal relay
Yes
Yes
Bit
1 bit
S0 - Annunciator
Yes
Yes
Bit
Default configuration:
DataBits: 8.
StopBits: 1 if parity is used, 2 if no parity.
Set the other fields according to your Serial or MultiSerial port configuration.
SlaveId: Set this field with the address of the slave device in the SNP network. They can be addressed from 1 to 247 for serial nodes, or 0 to 255 for TCP/IP nodes. The address 0 is used for the broadcast.
Station syntax: <SlaveId>
Ex: 1
Station syntax: <ComPort>;<SlaveId>
Where : <ComPort> = COM Port of the slave device in the SNP network (default is com1).
Ex: com1;1
The syntax for the Mitsubishi FX Serial SNP communication points isare: <Operand> <Address>Where :
Operand |
---|
D - Data register |
TN – Timer Current value |
TS – Timer Contact |
CN – Counter Current value |
CS – Counter Contact |
X - Input relay |
Y - Output relay |
M - Internal relay |
S0 - Annunciator |
Note: The Y Operand is an Octal Numeral System.
Operand: Indicates the memory area, the valid values are:
AI | Analog Input |
AQ | Analog Output |
G | Discrete Global Memory |
I | Discrete Input |
Q | Discrete Output |
T | Output (Temporary) Coils |
M | Internal Coils |
S | System Status |
R | Register Memory |
Address: Indicates the data address in the memory area.
Ex: %R00001 (Operand = R, Address = 1)
SNP Driver |
---|
Revision History | |
---|---|
Version | Notes |
1.0. |
0.0 | Initial release on new documentation standards |
Page Tree | ||
---|---|---|
|