Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.


Page properties
hiddentrue
idconnector-metadata


Property

Value

Sector

Automation Vendors

Group

MitsubishiAltus

ConnectorMitsubishi FX Serial

Altus Alnet I

Name

MitsubishiFXSerial

Devices compatible with Mitsubishi FX3U

Alnet




  • Name: MitsubishiFXSerial Alnet
  • Version: 1.14.0.1.0
  • Protocol: Proprietary Alnet I (Proprietary) 
  • Interface: Standard Serial Port
  • Runtime: Multiplatform.Net 4.8 (Windows)
  • Configuration:
    • Devices / Protocols

Table of Contents
maxLevel2
minLevel2
stylenone



Overview

Communication with devices compatible with Mitsubishi FX3U

Devices compatible with Alnet I protocol.

Communication Driver Information

Driver name

Alnet

Assembly Name

T.ProtocolDriver.Alnet

Assembly Version

1.14.0.0

Available for Linux

False

Devices supported 

AL-2000 family

Manufacturer

Altus

Protocol

Alnet I (Proprietary)

PC Requirements

Serial or MultiSerial



Supported Operands


Operand

Read

Write

Bit Read

Bit Write

Data Type

Address size

D - Data register

E - Input Octet

Yes

Yes

Yes

Yes

Byte

1 byte

S - Output Octet

Yes

Yes

Yes

Yes

Byte

1 byte

A - Auxiliary

Yes

Yes

Yes

Yes

Word

2 bytes

TN – Timer Current value

Byte

1 byte

M - Memory

Yes

Yes

Yes


Word

2 bytes

TS – Timer Contact

I - Integer

Yes

Yes

Yes

No


DWord

Bit

1 bit

CN – Counter Current value

4 bytes

D - Decimal

Yes

Yes

Yes

Word


LBCD

2

4 bytes

CS – Counter Contact

F - Real

Yes

No

Yes

Bit



Single

1 bit

4 bytes

X - Input relay

TM - Memory Table

Yes

Yes

No

Yes

Bit


Word

1 bit

2 bytes

Y - Output relay

TI - Integer Table

Yes

Yes

Yes

Bit


DWord

1 bit

4 bytes

M - Internal relay

TD - Decimal Table

Yes

Yes

Yes

Bit


LBCD

1 bit

4 bytes

S0

TF -

Annunciator

Real Table

Yes

Yes

Bit



Single

1 bit

4 bytes



Channels Configuration

Protocol Options

Maximum size of blocks

BlockSize: Defines the maximum

of addresses in a read block.

Protocol Options

  • Com – Define the Port of communication
  • Baud Rate – Define the rate at which information is transferred in a communication channel.
  • Databits – Define the number of data bits in each character
  • Parity – Define the method of detecting errors in transmission.
  • Stop bits – Define the stop bits.
  • DTR – Define a control signal in RS-232 serial communication.
  • RTS – Define the Request to Send
  • CTS – Define the Clear to Send
  • CtsWait – Time in milliseconds

Nodes Configuration

Primary Station 

amount of items per group, the default value is 248.

Family:  Set the PLC family. It can be:

  • 2000:For the AL-2000 series.

EventsTableSize: Size of the events table for unsolicited messages. Default value: 64.

EventsDataSource: Source of events: "PLC" (default) or "Computer".

Trace: Enables/disables communication debug logs. Default: "Disabled".


Nodes Configuration

Station Configuration 

There is no station configuration for the Altus Alnet-I driver

SlaveID: The default is 1

.


Points Configuration

The syntax for the Mitsubishi FX Serial Alnet communication points isare: <Operand> <Address>Where :

  • %<Operand><Address>
  • <Operand>: Represents the Device Memory :
  • <Address>: Address number

Operand

D - Data register

TN – Timer Current value

TS – Timer Contact

CN – Counter Current value

CS – Counter Contact

X - Input relay

Y - Output relay

M - Internal relay

S0 - Annunciator

Note: The Y Operand is an Octal Numeral System.

Operand: Indicates the memory area, the valid values are:

Operand

Read

Write

Bit Read

Bit Write

Data Type

Address size

E - Input Octet

Yes

Yes

Yes

Yes

Byte

1 byte

S - Output Octet

Yes

Yes

Yes

Yes

Byte

1 byte

A - Auxiliary

Yes

Yes

Yes

Yes

Byte

1 byte

M - Memory

Yes

Yes

Yes


Word

2 bytes

I - Integer

Yes

Yes

Yes


DWord

4 bytes

D - Decimal

Yes

Yes

Yes


LBCD

4 bytes

F - Real

Yes

Yes



Single

4 bytes

Address: Indicates the data address in the memory area.

Ex: %E0000 (Operand = E, Address = 0)

  • %<Operand><TableId>[TablePosition]

Operand: Indicates the memory area, the valid values are:

Operand

Read

Write

Bit Read

Bit Write

Data Type

Address size

TM - Memory Table

Yes

Yes

Yes


Word

2 bytes

TI - Integer Table

Yes

Yes

Yes


DWord

4 bytes

TD - Decimal Table

Yes

Yes

Yes


LBCD

4 bytes

TF - Real Table

Yes

Yes



Single

4 bytes

TableId: Indicates the table memory area.

TablePosition: Indicates the position in table memory area.

Ex: %TM0001[2] (Operand = TM, TableId = 1 TablePosition = 2)




Driver Revision History

Alnet Driver

Driver Revision History

MitsubishiFX_Serial

Revision History

Version 

Notes

1.14.0

.1

.0

Initial release on new documentation standards



In this section...