Communication with devices compatible with Mitsubishi FX3U
Operand
Read
Write
Data Type
Address size
D - Data register
Yes
Yes
Word
2 bytes
TN – Timer Current value
Yes
Yes
Word
2 bytes
TS – Timer Contact
Yes
No
Bit
1 bit
CN – Counter Current value
Yes
Yes
Word
2 bytes
CS – Counter Contact
Yes
No
Bit
1 bit
X - Input relay
Yes
No
Bit
1 bit
Y - Output relay
Yes
Yes
Bit
1 bit
M - Internal relay
Yes
Yes
Bit
1 bit
S0 - Annunciator
Yes
Yes
Bit
1 bit
EXCOM protocol.
Communication Driver Information | |
---|---|
Driver name | EXCOM |
Assembly Name | T.ProtocolDriver.EXCOM |
Assembly Version | 1.1.0.0 |
Available for Linux | False |
PLC types supported | PLCs ABB Masterpiece 200, MasterGate 210 / 230, Advant Controller AC 400 / AC 450 |
Manufacturer | ABB |
Interface | Serial and MultiSerial (RS232) |
Default configuration:
DataBits: 8.
StopBits: 1 if parity is used, 2 if no parity.
Set the other fields according to your Serial or MultiSerial port configuration.
Network: Network identifier for multi-station communication (0-99).
Node: Node address within the network (0-99).
Syntax: <Network>;<Node>
Ex: 1;3
The syntax for the Mitsubishi FX Serial EXCOM communication points is: <Operand> <Dataset Files> <Address>
Where :
Operand |
---|
D - Data register |
TN – Timer Current value |
TS – Timer Contact |
CN – Counter Current value |
CS – Counter Contact |
X - Input relay |
Y - Output relay |
M - Internal relay |
S0 - Annunciator |
EXCOM Revision History | |
---|---|
Version | Notes |
1 |
.1 |
Initial release on new documentation standards. |