AB RockwellMicroLogix 1100 and 1400 devices
- Name: DF1Serial
- Version
This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module.
On this page:
Table of Contents | ||||||
---|---|---|---|---|---|---|
|
Summary
DF1 Serial driver implements communication with Rockwell / Allen-Bradley devices using DF1 Protocol (SLC Families, and Micrologix) via Serial communication. It operates as a Master on serial networks. The communications blocks are dynamically created according to the pooling cycle defined on the AccessType for each Device Point.
Communication Driver Information
Driver name
DF1 Serial
Assembly Name
T.ProtocolDriver.DF1Serial
Assembly Version
- 1.0.1.2
- Protocol: DF1
- Interface: Serial RS-232
- Runtime: .NET 2.0 (Multiplatform)
- Configuration:
- Devices / Protocols
On this Page:
Table of Contents | ||||||
---|---|---|---|---|---|---|
|
Module Configuration
This document has only information about the device connection settings and its address syntax.
For further Information, see:
Available for Linux
False
Devices supported
SLC Families / Micrologix
Manufacturer
Rockwell / Allen-Bradley
Protocol
Serial
PC Requirements
Supported Files
Files | Read | Write | Data Type | Address size |
N | Yes | Yes | Word | 2 bytes |
B | Yes | Yes | Bit | 1 bit |
F | Yes | Yes | Single | 4 bytes |
O | Yes | Yes | Output | 1 bit |
I | Yes | Yes | Input | 1 bit |
Channels Configuration
Protocol Options
CheckSum: It defines the checksum currently being used by the device, whether it is CRC or BCC.
Settings
Set the fields according to your serial port configuration.
Nodes Configuration
Station Configuration
SlaveId: Set this field with the address of the slave device in the network.
Points Configuration
Point Address Configuration
The syntax for the DF1 Serial communication point is: <FileType><FileNumber>:<Address>
Where <FileType> indicates the memory area, the valid values are:
- N, for Integer
- B, for digital
- F, for real
<FileNumber> indicates the data address for the chosen file (up to 255).
<Address> indicates the address from the specific file which will read and/or write from PLC.
For I/O, the syntax is: <FileType>:<Slot>/<Address>
- O, for digital (output)
- I, for digital (input)
<Slots> indicates the position where the I/O module is connected to on the PLC
E.g.:
- F8:0
- N21:1
- B21:1/6
- I:0/0
Driver Revision History
DF1 Serial Revision History | |
---|---|
Version | Notes |
1.0.1.2 | Initial release on new documentation standards. |