Alarms & Audit-Trail (Tutorial) teaches you to:

  • Create alarm groups and items
  • Configure alarm conditions
  • Set up notifications
  • Enable audit trail for FDA 21 CFR Part 11 compliance

Prerequisites:

In this page:

Table of Contents
maxLevel2
minLevel2
indent10px
excludeSteps
stylenone




Alarms Tutorial | Concept | How-to Guide | Reference

What You'll Learn

  • Create alarm groups and items
  • Configure alarm conditions
  • Set up notifications
  • Enable audit trail

Step 1:

Create

Configure Alarm Groups

  1. Navigate to Alarms → Groups
  2. Add Verify pre-defined groups exist:

Critical Alarms:

  • Name: Critical
  • Priority: 1
  • Acknowledgment: Required
  • Sound: Critical.wav
  • Color: Red

Warnings:

  • Name: Warnings
  • Priority: 3
  • Acknowledgment: Optional
  • Color: Yellow


GroupAckRequiredLogEventsPriority
CriticalTrueTrueHigh
WarningFalseTrueMedium
AuditTrailFalseTrueHidden


Modify Critical group:

    • Open the ComboBox Sound field
    • Select Exclamation
    • Press Enter

Step 2: Create

Step 2: Define

Alarm Items

  1. Go to Alarms → Items
  2. Create Add high temperature alarm:

High Temperature:

  • Name: Tank1_HighTemp
  • Group: Critical
  • Tag: Tank1_Temperature
  • Condition: Greater than
  • Limit: 85
  • Message: "Tank 1 temperature exceeds limit"
  • Deadband: 2

Low Level:

  • Name: Tank1_LowLevel
  • Group: Warnings
  • Tag: Tank1_Level
  • Condition: Less than
  • Limit: 10
  • Message: "Tank 1 level low"

Step 3: Configure Deviation Alarms

For rate-of-change monitoring:

  • Name: Pressure_Deviation
  • Type: Deviation
  • Tag: Line_Pressure
  • Setpoint Tag: Pressure_Setpoint
  • Deviation: ±10
  • Time: 60 seconds

Step 4: Set Up Email Notifications

  1. Navigate to Alarms → Groups
  2. Select group → Email settings:
PropertyValue
TagNameTag.TankFarm/Tank1/Temp
ConditionHiHi
Limit85
GroupCritical
MessageTank 1 Critical Temperature: {Tag.TankFarm/Tank1/Temp}°C
Priority100
  1. Add low level alarm:
PropertyValue
TagNameTag.ankFarm/Tank1/Level
ConditionLo
Limit20
GroupWarning
MessageTank 1 Low Level Warning
Priority50

Step 3: Configure Alarm Areas

  1. Navigate to Alarms → Areas
  2. Create hierarchy:
  • Plant
    • Production
      • Tank1
      • Tank2
    • Utilities
  1. Assign alarms to areas:
    • Return to Alarms → Items
    • Set Area = Plant.Production.Tank1 for both alarms

Step 4: Enable

Step 5: Configure

Audit Trail

  1. Go to Alarms → Global Settings
  2. In Audit Trail section:
    • Check Enable
    logging
    • Audit Trail
    • Enable options:
        Login/Logout: Yes
        • User Logon/Logoff
        • Tag Changes
        : Yes
      • Alarm Acknowledgments: Yes
      • Configuration Changes: Yes
    • Set storage:
      • Database: SQL Server
      • Table: AuditTrail
      • Retention: 365 days

Step 6: Create Alarm Areas

For plant organization:

  1. Alarms → Areas
  2. Create hierarchy:
Plant/
  ??? Production/
  ?   ??? Line1/
  ?   ??? Line2/
  ??? Utilities/
      ??? Boilers/
      ??? Compressors/
  1. Assign alarms to areas

Step 7: Test Alarms

  1. Start Runtime
  2. Open Alarms → Online
  3. Force tag values to trigger alarms
  4. Verify:
    • Alarm appears in list
    • Color coding correct
    • Sound plays
    • Email sent

Step 8: Alarm Summary Display

Create operator display:

  1. Displays → New
  2. Add AlarmViewer control
  3. Configure:
    • Show: Active alarms
    • Columns: Time, Area, Message, Value
    • Filter: By area or priority
    • Allow: Acknowledge, silence

FDA 21 CFR Part 11 Setup

For compliance:

  • Electronic signatures on acknowledgments
  • Audit trail cannot be disabled
  • User authentication required
  • Time synchronization enabled
  • Data integrity checksums

Best Practices

  • Use consistent naming conventions
  • Set appropriate priorities (1-5)
  • Include clear messages
  • Test all alarm conditions
  • Document alarm philosophy
  • Regular alarm rationalization

Next Steps

  • [Historian] - Store alarm history
  • [Reports Module] - Alarm reports
  • [Security Module] - User permissions
        • Operator Actions
        • Custom Messages
    1. Configure database retention:
      • Life Time: 2555 days (7 years for FDA compliance)

    Step 5: Create Alarm Display

    1. Navigate to Displays → New
    2. Name: AlarmMonitor
    3. Add AlarmViewer control from toolbox
    4. Configure properties:
      • List: OnlineAlarms
      • ShowAcknowledged: False
      • Columns: Time, TagName, Message, Value, Group
    5. Add AlarmArea control for navigation
    6. Save display

    Step 6: Test Alarms

    1. Start Runtime (Runtime → Startup)
    2. Open Runtime → Online Alarms
    3. Simulate alarm conditions:

    csharp

    // In Script Task or Watch Window
    @Tag.Tank1_Temp = 90;  // Triggers high temp
    @Tag.Tank1_Level = 15; // Triggers low level
    1. Verify in AlarmViewer:
      • Critical alarm shows red
      • Warning shows yellow
      • Sound plays for Critical
      • Acknowledge required for Critical
    2. Test acknowledgment:
      • Right-click Critical alarm
      • Select Acknowledge
      • Verify state change

    Step 7: Verify Audit Trail

    1. Change AlarmViewer List to AuditTrail
    2. Verify logged events:
      • User login
      • Alarm triggers
      • Acknowledgments
      • Tag changes
    3. Add custom message via script:

    csharp

    @Alarm.GlobalSettings.AuditTrail.AddCustomMessage(
        "Tutorial test completed by " + @Client.UserName
    );

    Next Steps

    • [Configure Email Notifications] - Set up SMTP
    • [Create Alarm Reports] - Historical analysis
    • [FDA Compliance Setup] - Full 21 CFR Part 11

    Step-by-step guide to configure alarm groups, conditions, notifications, and audit trail for operational monitoring and FDA compliance.


    In this section...

    Page Tree
    root@parent
    spaces93DRAF