Alarms & Audit-Trail (Tutorial) teaches you to:
- Create alarm groups and items
- Configure alarm conditions
- Set up notifications
- Enable audit trail for FDA 21 CFR Part 11 compliance
Prerequisites:
- Add Tags to UNS (Tutorial) - uses TankFarm tags
In this page:
Table of Contents maxLevel 2 minLevel 2 indent 10px exclude Steps style discnone
What You'll Learn
- Create alarm groups and items
- Configure alarm conditions
- Set up notifications
- Enable audit trail
Step 1:
CreateConfigure Alarm Groups
- Navigate to Alarms → Groups
- Add Verify pre-defined groups exist:
Critical Alarms:
- Name:
Critical
- Priority: 1
- Acknowledgment: Required
- Sound: Critical.wav
- Color: Red
Warnings:
- Name:
Warnings
- Priority: 3
- Acknowledgment: Optional
- Color: Yellow
Group | AckRequired | LogEvents | Priority |
---|---|---|---|
Critical | True | True | High |
Warning | False | True | Medium |
AuditTrail | False | True | Hidden |
Modify Critical group:
- Open the ComboBox Sound field
- Select Exclamation
- Press Enter
Step 2: Create
Step 2: DefineAlarm Items
- Go to Alarms → Items
- Create Add high temperature alarm:
High Temperature:
- Name:
Tank1_HighTemp
- Group:
Critical
- Tag:
Tank1_Temperature
- Condition: Greater than
- Limit: 85
- Message: "Tank 1 temperature exceeds limit"
- Deadband: 2
Low Level:
- Name:
Tank1_LowLevel
- Group:
Warnings
- Tag:
Tank1_Level
- Condition: Less than
- Limit: 10
- Message: "Tank 1 level low"
Step 3: Configure Deviation Alarms
For rate-of-change monitoring:
- Name:
Pressure_Deviation
- Type: Deviation
- Tag:
Line_Pressure
- Setpoint Tag:
Pressure_Setpoint
- Deviation: ±10
- Time: 60 seconds
Step 4: Set Up Email Notifications
- Navigate to Alarms → Groups
- Select group → Email settings:
- SMTP Server:
mail.company.com
- Port: 587
- From:
scada@company.com
- To:
operators@company.com
- Subject: "Critical Alarm: {AlarmName}"
- SMTP Server:
Property | Value |
---|---|
TagName | Tag.TankFarm/Tank1/Temp |
Condition | HiHi |
Limit | 85 |
Group | Critical |
Message | Tank 1 Critical Temperature: {Tag.TankFarm/Tank1/Temp}°C |
Priority | 100 |
- Add low level alarm:
Property | Value |
---|---|
TagName | Tag.ankFarm/Tank1/Level |
Condition | Lo |
Limit | 20 |
Group | Warning |
Message | Tank 1 Low Level Warning |
Priority | 50 |
Step 3: Configure Alarm Areas
- Navigate to Alarms → Areas
- Create hierarchy:
- Plant
- Production
- Tank1
- Tank2
- Utilities
- Production
- Assign alarms to areas:
- Return to Alarms → Items
- Set Area =
Plant.Production.Tank1
for both alarms
Step 4: Enable
Step 5: ConfigureAudit Trail
- Go to Alarms → Global Settings
- In Audit Trail section:
- Check Enable Audit Trail
- Enable
- options:
- User Logon/Logoff
- Tag Changes
- Alarm Acknowledgments: Yes
- Configuration Changes: Yes
- Set storage:
- Database: SQL Server
- Table: AuditTrail
- Retention: 365 days
Step 6: Create Alarm Areas
For plant organization:
- Alarms → Areas
- Create hierarchy:
Plant/
??? Production/
? ??? Line1/
? ??? Line2/
??? Utilities/
??? Boilers/
??? Compressors/
- Assign alarms to areas
Step 7: Test Alarms
- Start Runtime
- Open Alarms → Online
- Force tag values to trigger alarms
- Verify:
- Alarm appears in list
- Color coding correct
- Sound plays
- Email sent
Step 8: Alarm Summary Display
Create operator display:
- Displays → New
- Add AlarmViewer control
- Configure:
- Show: Active alarms
- Columns: Time, Area, Message, Value
- Filter: By area or priority
- Allow: Acknowledge, silence
FDA 21 CFR Part 11 Setup
For compliance:
- Electronic signatures on acknowledgments
- Audit trail cannot be disabled
- User authentication required
- Time synchronization enabled
- Data integrity checksums
Best Practices
- Use consistent naming conventions
- Set appropriate priorities (1-5)
- Include clear messages
- Test all alarm conditions
- Document alarm philosophy
- Regular alarm rationalization
Next Steps
- Operator Actions
- Custom Messages
- Configure database retention:
- Life Time: 2555 days (7 years for FDA compliance)
Step 5: Create Alarm Display
- Navigate to Displays → New
- Name:
AlarmMonitor
- Add AlarmViewer control from toolbox
- Configure properties:
- List: OnlineAlarms
- ShowAcknowledged: False
- Columns: Time, TagName, Message, Value, Group
- Add AlarmArea control for navigation
- Save display
Step 6: Test Alarms
- Start Runtime (Runtime → Startup)
- Open Runtime → Online Alarms
- Simulate alarm conditions:
csharp
// In Script Task or Watch Window
@Tag.Tank1_Temp = 90; // Triggers high temp
@Tag.Tank1_Level = 15; // Triggers low level
- Verify in AlarmViewer:
- Critical alarm shows red
- Warning shows yellow
- Sound plays for Critical
- Acknowledge required for Critical
- Test acknowledgment:
- Right-click Critical alarm
- Select Acknowledge
- Verify state change
Step 7: Verify Audit Trail
- Change AlarmViewer List to
AuditTrail
- Verify logged events:
- User login
- Alarm triggers
- Acknowledgments
- Tag changes
- Add custom message via script:
csharp
@Alarm.GlobalSettings.AuditTrail.AddCustomMessage(
"Tutorial test completed by " + @Client.UserName
);
Next Steps
- [Configure Email Notifications] - Set up SMTP
- [Create Alarm Reports] - Historical analysis
- [FDA Compliance Setup] - Full 21 CFR Part 11
Step-by-step guide to configure alarm groups, conditions, notifications, and audit trail for operational monitoring and FDA compliance.