Bosch Rexroth IndraControl L20/L40

  • Name: IndraControl
  • Version: 1.0.0.0
  • Protocol: EtherNet/IP - Bosch
  • Interface:TCP/IP
  • Runtime: Multiplatform
  • Configuration:
    • Devices / Protocols

On this Page:


Overview

IndraControl communication driver implements communication with Bosch Rexroth IndraControl L20/L40 PLCs using a EtherNet/IP adapter. 

Supported Data

Type

Read

Write

Data Type

EtherNet/IP Adapter Outputs

Yes

Yes

Byte Only

EtherNet/IP Adapter Inputs

Yes

-

Byte Only


Channel Configuration

Protocol Options

This configuration is required.


Node Configuration

Station Configuration

Stations syntax: <IP> ; <Port> ;

Where :

<IP>: IP address of the slave device in the network

<Port>: TCP port where the slave device is listening (default is 44818)

Sample Node configuration

Name

Channel

Primary Station

IndraControl

IndraControl

192.168.200.105;44818

 


Point Address Configuration

The syntax for the IndraControl communication points is: <%QB><Address> for Outputs and <%IB><Address> for Inputs

 E.g.: %QB1 (Type = Output, Address = 1)

 Sample Points Configuration

 

TagName

Node

Address

DataType

AccessType

Output1

IndraControl

%QB1

Native

ReadWrite

Output2

IndraControl

%QB2

Native

ReadWrite

Output3

IndraControl

%QB3

Native

ReadWrite

Output15

IndraControl

%QB15

Native

ReadWrite

Input1

IndraControl

%IB1

Native

Read

Input2

IndraControl

%IB2

Native

Read

 


Driver Revision History

IndraControl Revision History
Version Notes
1.0.0.0Initial release on new documentation standards.

In this section...