Alarms & Audit-Trail (Tutorial) teaches you to:

  • Create alarm groups and items
  • Configure alarm conditions
  • Set up notifications
  • Enable audit trail for FDA 21 CFR Part 11 compliance

Prerequisites:

In this page:



Alarms → Tutorial | Concept | How-to Guide | FDA 21 CRF 11 | Reference



Step 1: Configure Alarm Groups

  1. Navigate to Alarms → Groups
  2. Verify pre-defined groups exist:


GroupAckRequiredLogEventsPriority
CriticalTrueTrueHigh
WarningFalseTrueMedium
AuditTrailFalseTrueHidden


Modify Critical group:

    • Open the ComboBox Sound field
    • Select Exclamation
    • Press Enter

Step 2: Create Alarm Items

  1. Go to Alarms → Items
  2. Add high temperature alarm:
PropertyValue
TagNameTag.TankFarm/Tank1/Temp
ConditionHiHi
Limit85
GroupCritical
MessageTank 1 Critical Temperature: {Tag.TankFarm/Tank1/Temp}°C
Priority100
  1. Add low level alarm:
PropertyValue
TagNameTag.ankFarm/Tank1/Level
ConditionLo
Limit20
GroupWarning
MessageTank 1 Low Level Warning
Priority50

Step 3: Configure Alarm Areas

  1. Navigate to Alarms → Areas
  2. Create hierarchy:
  • Plant
    • Production
      • Tank1
      • Tank2
    • Utilities
  1. Assign alarms to areas:
    • Return to Alarms → Items
    • Set Area = Plant.Production.Tank1 for both alarms

Step 4: Enable Audit Trail

  1. Go to Alarms → Global Settings
  2. In Audit Trail section:
    • Check Enable Audit Trail
    • Enable options:
      • User Logon/Logoff
      • Tag Changes
      • Operator Actions
      • Custom Messages
  3. Configure database retention:
    • Life Time: 2555 days (7 years for FDA compliance)

Step 5: Create Alarm Display

  1. Navigate to Displays → New
  2. Name: AlarmMonitor
  3. Add AlarmViewer control from toolbox
  4. Configure properties:
    • List: OnlineAlarms
    • ShowAcknowledged: False
    • Columns: Time, TagName, Message, Value, Group
  5. Add AlarmArea control for navigation
  6. Save display

Step 6: Test Alarms

  1. Start Runtime (Runtime → Startup)
  2. Open Runtime → Online Alarms
  3. Simulate alarm conditions:

csharp

// In Script Task or Watch Window
@Tag.Tank1_Temp = 90;  // Triggers high temp
@Tag.Tank1_Level = 15; // Triggers low level
  1. Verify in AlarmViewer:
    • Critical alarm shows red
    • Warning shows yellow
    • Sound plays for Critical
    • Acknowledge required for Critical
  2. Test acknowledgment:
    • Right-click Critical alarm
    • Select Acknowledge
    • Verify state change

Step 7: Verify Audit Trail

  1. Change AlarmViewer List to AuditTrail
  2. Verify logged events:
    • User login
    • Alarm triggers
    • Acknowledgments
    • Tag changes
  3. Add custom message via script:

csharp

@Alarm.GlobalSettings.AuditTrail.AddCustomMessage(
    "Tutorial test completed by " + @Client.UserName
);

Next Steps

  • [Configure Email Notifications] - Set up SMTP
  • [Create Alarm Reports] - Historical analysis
  • [FDA Compliance Setup] - Full 21 CFR Part 11

Step-by-step guide to configure alarm groups, conditions, notifications, and audit trail for operational monitoring and FDA compliance.