Rockwell MicroLogix 1100 and 1400 devices
Driver Name: DF1Serial
Version: 1.0.1.2
Multiplatform runtime

Modules: Device

Manufacturer: Allen-Bradley / Rockwell
Protocol: DF1 over Serial
PC Requirements: RE-232 serial port


Module Configuration

This document has only information about the device connection settings and its address syntax.

For further Information, see:

Supported Files

Files

Read

Write

Data Type

Address size

N

Yes

Yes

Word

2 bytes

B

Yes

Yes

Bit

1 bit

F

Yes

Yes

Single

4 bytes

O

Yes

Yes

Output

1 bit

I

Yes

Yes

Input

1 bit


Channels Configuration

Protocol Options

CheckSum: It defines the checksum currently being used by the device, whether it is CRC or BCC. 

Settings

Set the fields according to your serial port configuration.



Nodes Configuration

Station Configuration

SlaveId: Set this field with the address of the slave device in the network.



Points Configuration

Point Address Configuration

The syntax for the DF1 Serial communication point is: <FileType><FileNumber>:<Address>

Where <FileType> indicates the memory area, the valid values are:

  • N, for Integer
  • B, for digital
  • F, for real

<FileNumber> indicates the data address for the chosen file (up to 255).
<Address> indicates the address from the specific file which will read and/or write from PLC.

For I/O, the syntax is: <FileType>:<Slot>/<Address>

  • O, for digital (output)
  • I, for digital (input)

<Slots> indicates the position where the I/O module is connected to on the PLC

E.g.:

  • F8:0
  • N21:1
  • B21:1/6
  • I:0/0