Mitsubishi FX Series  and compatible

  • Name: MelsecFX
  • Version: 1.0.1.0
  • Protocol: Melsec Q 1E frame
  • Interface: TCP/IP
  • Runtime: Multiplatform
  • Configuration:
    • Devices / Protocols

On this page:


Overview

MelsecFX communication driver implements communication with Mitsubishi FX Series PLCs using Melsec Q 1E frame. It operates as a Master on TCP/IP networks. The communication blocks are dynamically created according to the pooling cycle defined on the AccessType for each point.




Supported Operands

Operand

Read

Write

Data Type

Address size

D - Data register

Yes

Yes

Short

2 bytes

W - Link register

Yes

Yes

Short

2 bytes

R - File register

Yes

Yes

Short

2 bytes

TN – Timer Current value

Yes

Yes

Short

2 bytes

TS – Timer Contact

Yes

Yes

Bit

1 bit

TC – Timer Coil

Yes

Yes

Bit

1 bit

CN – Counter Current value

Yes

Yes

Short

2 bytes

CS – Counter Contact

Yes

Yes

Bit

1 bit

CC – Counter Coil

Yes

Yes

Bit

1 bit

X - Input relay

Yes

Yes

Bit

1 bit

Y - Output relay

Yes

Yes

Bit

1 bit

M - Internal relay

Yes

Yes

Bit

1 bit

B - Link relay

Yes

Yes

Bit

1 bit

F - Annunciator

Yes

Yes

Bit

1 bit


Channel Configuration

Protocol Options

  • Maximum size of blocks: Defines the maximum of addresses in a read block.

 Settings

TCP/IP:

  • NodeConnections: Defines the maximum number of parallel requests that will be sent to each node (asynchronous communication)



Node Configuration

Station Configuration

TCP/IP:

  • Station syntax: <IP address> ; <Port number>

Where :

  • <IP address>: IP address of the slave device in the modbus network
  • <Port number>: TCP port where the slave device is listening (default is 44818)

E.g.: 192.168.1.1 ; 5551



Points Configuration

The syntax for the MelsecFX communication points is: <Operand> <Address>

Where :

  • <Operand>: Represents the Device Memory :
  • <Address>: Address number

Operand

D - Data register

W - Link register

R - File register

TN – Timer Current value

TS – Timer Contact

TC – Timer Coil

CN – Counter Current value

CS – Counter Contact

CC – Counter Coil

X - Input relay

Y - Output relay

M - Internal relay

B - Link relay

F - Annunciator


Driver Revision History

MelsecFX Revision History

Version 

Notes

1.0

Initial release on new documentation standards.


In this section...

Error rendering macro 'pagetree'

null

  • No labels