S7 300/400/1200/1500
- Name: Siemens
- Version: 2.2.2.0
- Protocol: Proprietary
- Interface: TCP/IP
- Runtime: .NET 4.8 (Windows)
- Configuration:
- Devices / Protocols
On this page:
Overview
Communication Driver Information | |
---|---|
Driver name | Siemens |
Assembly Name | T.ProtocolDriver.Siemens |
Assembly Version | 2.2.2.0 |
Available for Linux | False |
Devices supported | S7 300/400/1200/1500 |
Third-party libraries | AGL4DotNET.dll, AGLink40.dll and AGLink40_x64.dll. |
Manufacturer | Siemens |
Protocol | Proprietary over TCP/IP |
PC Requirements | Ethernet port |
The TwinCAT communication driver is supported only in Windows Solutions.
Channel Configuration
Protocol Options
- Device Number: Used for connection when there is more than one PLC in the network.
- PLC Number: Slave PLC number
Node Configuration
Station Configuration
Station syntax: <IP Address> ; <Rack>; <Slot>;<S7 Family>
- <IP Address>: IP address of the slave device in the Siemens network
- <Rack>: Rack of the device
- <Slot>: Slot of the device
- <S7 Family>: Model of the device. The options are:
300/400: Support for PLC Siemens S7-300 and S7-400 Series
1200: Support for PLC Siemens S7-1200 and S7-1500 Series
Points Configuration
Address
The syntax for the Siemens communication points is: <Type>:<Format><Address>.< Bit or String Length >
For DataBlock type: DB<DB Group>:<Format><Address>.<Bit or String Length>
Where:
- <Type> is the register type. Valid values are:
- M=Flags
- T=Timers
- C=Counters
- I=Inputs
- Q=Outputs
- DB=Data Blocks.
- <DB Group> is the group number of the configured Data Block type.
- <Address> is the device address.
- <Format> is the format to treat the value from or to the device. Valid values are:
- B=Byte
- W=Word
- DW=Dword
- F=Float
- ST=String
- <Bit or String Length> is the bit number. This parameter is optional. If you use the String type, it represents the String length.
Error Code Reference
Hex | Decimal (signed) | Description |
---|---|---|
0x00000000 | 0 | No error |
0x00000001 | 1 | No error, job still in process |
0xFFF00000 | -1048576 | Function not implemented |
0xFFF00001 | -1048575 | Parameter error when calling function |
0xFFF00002 | -1048574 | Invalid device number |
0xFFF00003 | -1048573 | Invalid PLC number |
0xFFF00004 | -1048572 | Invalid parameter type |
0xFFF00005 | -1048571 | Insufficient memory |
0xFFF00006 | -1048570 | Device already opened |
0xFFF00007 | -1048569 | Device not opened |
0xFFF00008 | -1048568 | Job already removed |
0xFFF00009 | -1048567 | Invalid job number |
0xFFF0000A | -1048566 | Function not supported |
0xFFF0000B | -1048565 | Adapter not initialized |
0xFFF0000C | -1048564 | No free connections available |
0xFFF0000D | -1048563 | Device not configured or not supported |
0xFFF0000E | -1048562 | Hardware not found |
0xFFF0000F | -1048561 | Error when reading parameters |
0xFFF00010 | -1048560 | Error when writing parameters |
0xFFF00011 | -1048559 | Demo period expired |
0xFFF00012 | -1048558 | Wrong character in text. Conversion not possible |
0xFFF00013 | -1048557 | Buffer is not long enough |
0xFFF00014 | -1048556 | File not found |
0xFFF00015 | -1048555 | Error when calling configuration program |
0xFFF00016 | -1048554 | Error when loading DLL dynamically |
0xFFF00017 | -1048553 | Could not create file |
0xFFF50000 | -720896 | No free job buffer available |
0xFFF50001 | -720895 | Invalid packet |
0xFFF50002 | -720894 | No connection to PLC |
0xFFF50003 | -720893 | Connection closed |
0xFFF50004 | -720892 | Timeout |
0xFFF50005 | -720891 | Invalid context |
0xFFF50006 | -720890 | PLC memory error |
0xFFF50007 | -720889 | Invalid operating state |
0xFFF50008 | -720888 | Invalid address on PLC |
0xFFF50009 | -720887 | Invalid mode |
0xFFF5000A | -720886 | No data available e.g. DB is missing |
0xFFF5000B | -720885 | Priority class associated to OB does not exist |
0xFFF5000C | -720884 | Empty blocklist |
0xFFF5000D | -720883 | Block size error |
0xFFF5000E | -720882 | Invalid block number |
0xFFF5000F | -720881 | Protection level of function not sufficient |
0xFFF50010 | -720880 | Unknown SSL-ID (e.g. access to CP instead of PLC) |
0xFFF50011 | -720879 | Unknown SSL-index (e.g. access to CP instead of PLC) |
0xFFF50012 | -720878 | Information currently not ascertainable |
0xFFF50013 | -720877 | Unknown error message from PLC (please report!) |
0xFFF50014 | -720876 | Hardware error e.g. not available periphery |
0xFFF50015 | -720875 | Object access not allowed |
0xFFF50016 | -720874 | Context not supported |
0xFFF50017 | -720873 | Type (data type) not supported |
0xFFF50018 | -720872 | Internal error, please report |
0xFFF50019 | -720871 | Error rebooting PLC |
0xFFF5001A | -720870 | Error restarting PLC |
0xFFF5001B | -720869 | Connection end received |
0xFFF5001C | -720868 | PLC not found |
0xFFF5001D | -720867 | Too many data for this version of ACCON-AGLink |
0xFFF5001E | -720866 | PLC does not support this function |
0xFFF5001F | -720865 | Wrong Password |
0xFFF50020 | -720864 | Connection already legitimated |
0xFFF50021 | -720863 | Legitimation already released |
0xFFF50022 | -720862 | Password not neccessary |
0xFFF50023 | -720861 | At least one variable address invalid |
0xFFF50024 | -720860 | Job does not exist |
0xFFF50025 | -720859 | Invalid job state |
0xFFF50026 | -720858 | Invalid cycle time |
0xFFF50027 | -720857 | No more cyclic job possible |
0xFFF50028 | -720856 | Function not posible for this job (invalid state) |
0xFFF50029 | -720855 | Function abort (overload) |
0xFFF5002A | -720854 | No data for this variable |
0xFFF5002B | -720853 | Wrong time format |
0xFFF5002C | -720852 | Unknown PI name |
0xFFF5002D | -720851 | File transfer canceled by NCK |
0xFFF5002E | -720850 | Response too large for PDU size |
0xFFF5002F | -720849 | No H-PLC found |
0xFFF50030 | -720848 | Data not changed |
0xFFF30000 | -852968 | Error when reading device information |
0xFFF30001 | -852967 | Error when reading bus parameters |
0xFFF30002 | -852966 | Error when writing bus parameters |
0xFFF30003 | -852965 | No resources available on device |
0xFFF30004 | -852964 | Invalid device |
0xFFF30005 | -852963 | Adapter not found |
0xFFF30006 | -852962 | Needed device driver not found |
0xFFF20000 | -917504 | The desired adapter address already exists |
0xFFF20001 | -917503 | Invalid HSA (smaller than biggest active participant) |
0xFFF20002 | -917502 | Adapter is not in the logical ring |
0xFFF20004 | -917500 | Received package has wrong content |
0xFFF20006 | -917498 | Unknown error number from adapter |
0xFFF20007 | -917497 | Unknown error number from device driver |
0xFFF20008 | -917496 | Communications adapter has been removed |
0xFFF20009 | -917495 | Modem has been removed |
0xFFF2000A | -917494 | No directly connected PLC found |
0xFFF20313 | -916717 | Invalid speed on MPI bus |
0xFFF20314 | -916716 | Address is bigger than HSA |
0xFFF20315 | -916715 | The desired adapter address already exists |
0xFFF2031A | -916710 | No other active bus participants found |
0xFFF2031C | -916708 | Bus is jammed |
0xFFF2031D | -916707 | Bus is jammed |
0xFFF2031E | -916706 | Automatic detection of bus profile doesn't work, missing bus parameter telegram |
0xFFF20337 | -916681 | Legitimation missing |
0xFFF10000 | -983040 | COM-Port already used |
0xFFF10001 | -983039 | Modem not found |
0xFFF10002 | -983038 | Modem not onhook |
0xFFF10003 | -983037 | Modem not offhook |
0xFFF10004 | -983036 | Error in basic initialisation |
0xFFF10005 | -983035 | Error in Initstring 1 |
0xFFF10006 | -983034 | Error in Initstring 2 |
0xFFF10007 | -983033 | Error in Initstring 3 |
0xFFF10008 | -983032 | Error in Initstring 4 |
0xFFF10009 | -983031 | Error in dialtype sequence |
0xFFF1000A | -983030 | Error in dialtone sequence |
0xFFF1000B | -983029 | Error in autoanswer sequence |
0xFFF1000C | -983028 | Modem has been removed |
0xFFF1000D | -983027 | Connection could not be established |
0xFFF1000E | -983026 | Login denied. Unknown user. |
0xFFF1000F | -983025 | Login denied. Wrong password. |
0xFFF10010 | -983024 | Login denied. Callback number defined in adapter. |
0xFFF10011 | -983023 | Error while dialing |
0xFFF80000 | -524288 | Function not allowed |
0xFFF80001 | -524287 | Invalid project handle |
0xFFF80002 | -524286 | Error opening project |
0xFFF80003 | -524285 | Error creating program instance of project |
0xFFF80004 | -524284 | Error closing project |
0xFFF80005 | -524283 | No resp. no more programs found |
0xFFF80006 | -524282 | Program not found |
0xFFF80007 | -524281 | At least one of the specified parameters is invalid |
0xFFF80008 | -524280 | Runtime has expired (demo version) |
0xFFF8000A | -524278 | No resp. invalid data specified |
0xFFF8000B | -524277 | The program selected has no symbol table |
0xFFF8000C | -524276 | Symbol table already opened |
0xFFF8000D | -524275 | No resp. no more symbol entry found |
0xFFF8000E | -524274 | Error reading symbol entry |
0xFFF8000F | -524273 | Symbol not found |
0xFFF80010 | -524272 | Operand not found |
0xFFF80011 | -524271 | Invalid symbol |
0xFFF80012 | -524270 | Invalid operand |
0xFFF80013 | -524269 | Invalid filter string |
0xFFF80014 | -524268 | Data block (DB) not present |
0xFFF80015 | -524267 | Error reading DB block data |
0xFFF80016 | -524266 | Error parsing DB block data |
0xFFF80017 | -524265 | An opened DB is already present |
0xFFF80018 | -524264 | No opened DB present |
0xFFF80019 | -524263 | No resp. no more DB component found |
0xFFF8001A | -524262 | Specified DB component not found |
0xFFF8001B | -524261 | Specified DB component is invalid |
0xFFF8001C | -524260 | Specified DB component not matching |
0xFFF8001E | -524258 | Invalid constant |
0xFFF8001F | -524257 | Invalid constant size or format |
0xFFF80020 | -524256 | Object type initialization failed |
0xFFF80021 | -524255 | Invalid version of message configuration |
0xFFF80022 | -524254 | Error opening message configuration |
0xFFF80023 | -524253 | Error closing message configuration |
0xFFF80024 | -524252 | No resp. no more message entry found |
0xFFF80025 | -524251 | No resp. no more language found |
0xFFF80026 | -524250 | Database access error |
0xFFF80027 | -524249 | Invalid signal number |
0xFFF80028 | -524248 | Invalid add. value specification |
0xFFF80029 | -524247 | Add. value number invalid |
0xFFF8002A | -524246 | Element type of add. value invalid |
0xFFF8002B | -524245 | Add. value data length invalid |
0xFFF8002C | -524244 | Format specification missing |
0xFFF8002D | -524243 | Format specification invalid |
0xFFF8002E | -524242 | No resp. no more text library found |
0xFFF8002F | -524241 | No resp. no more text library entry found |
Driver Revision History
Siemens Revision History | |
---|---|
Version | Notes |
2.2.2.0 | Initial release on new documentation standards. |