You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 5 Next »

PLC5 or SLC500 using 1756-DHRIO
Driver Name: DHRIO
Version: 1.1.0.5
Multiplatform runtime

Modules: Device

Manufacturer: Allen-Bradley / Rockwell
Protocol: DH+ network
Interface: TCP/IP


 On This Page:


Module Configuration

This document has only information about the device connection settings and its address syntax.

For further Information, see:


Channels Configuration

Protocol Options

Model: Select the PLC Model, 5 or 500.



Nodes Configuration

Station Configuration

Station syntax:  <IP > ; <Port > ;<BackPlane>;<DHRIO Slot>;<DHRIO Channel>;<DH+ Node>

Where :

  •  <IP> = IP address of the ControlLogix device in the network.
  • <Port> = TCP port where the ControlLogix device is listening (default is 44818).
  • <BackPlane> = Used BackPlane in the device.
  • <DHRIO Slot> = Used slot for the 1756-DHRIO module in ControlLogix.
  • <DHRIO Channel> = Used channel  for the 1756-DHRIO module in ControlLogix.
  • <DH+ Node> = Used node in the DH+ network.

Station Example

PrimaryStation =  192.168.1.101 ; 44818 ; 1 ; 2 ; A ; 0



Points Configuration

Address

The syntax for the AB Ethernet communication points is: <FileType><FileNumber>:<Address>[Parameter]

  • <FileType>: the valid values are:                

File

Read

Write

Bit Read

Bit Write

Data Type

Address size

N             Integer

Yes

Yes

Yes

Yes

Word

2 bytes

B             Binary

Yes

Yes

Yes

Yes

Word

2 bytes

F              FloatPoint

Yes

Yes

Yes

Yes

Single

4 bytes

O             OutputLogical

Yes

Yes

Yes

Yes

Word

2 bytes

I               InputLogical

Yes

-

Yes

-

Word

2 bytes

S              Status

Yes

Yes

Yes

-

Word

2 bytes

T              Timer (Model 500 only)

Yes

Yes

-

-

Word or Bit

2 bytes or 1bit

R             Control (Model 500 only)

Yes

Yes

-

-

Word or Bit

2 bytes or 1bit

C             Counter (Model 500 only)

Yes

Yes

-

-

Word or Bit

2 bytes or 1bit

 

FileNumber: File number related to the FileType.

Address: element address in configured File.

Parameter: Aditional parameter for Timer, Control and Counter.

            Ex.: .Len, .Pre, .ACC, .EN, .TT, .DN, etc

Address Example

Address = N7:10



Driver Revision History

DHRIO Revision History

Version 

Notes

1.1.0.5

Initial release on new documentation standards.


In this section...

Error rendering macro 'pagetree'

null

  • No labels