You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 4 Current »

Mitsubishi Serie Q devices

  • Name: MitsubishiQ
  • Version: 1.0.6.0
  • Protocol: MELSEC 
  • Interface: TCP/IP
  • Runtime: Multiplatform
  • Configuration:
    • Devices / Protocols

On this page:


Overview

MitsubishiQ driver implements communication with Mitsubishi Serie Q devices on TCP/IP networks. The communications blocks are dynamically created according to the pooling cycle defined on the AccessType for each Device Point.


Channel Configuration

Protocol Options

  • BlockSize: Defines the maximum amount of items per group, the default value is 255.
  • Format: Defines the MELSEC protocol format, default value is 3E.



Node Configuration

Station Configuration

Station syntax: <IP address> ; <Port number>

 Where :

  •  <IP address>: IP address of the Mitsubishi device in the network
  • <Port number>: TCP port where the Mitsubishi device is listening (default is 5001)

E.g.:  192.168.1.101; 5001



Points Configuration

The syntax for the MitsubishiQ communication points is: <Operand><Address>

Where:

  • <Operand>: indicates the memory area into the Mitsubishi device:
  • <Address>: indicates address to communicate.

Operand

Description

X

Input

Y

Output

M

Internal relay

L

Latch relay

B

Link relay

F

Annunciator

V

Edge relay

SM

Special relay

TS

Timer (contact)

TC

Timer (coil)

CS

Counter (contact)

CC

Counter (coil)

TN

Timer (present value)

CN

Counter (present value)

D

Data register

R

File register

SD

Special  register

 

E.g.: D500, Y05



Driver Revision History

MitsubishiQ Revision History

Version 

Notes

1.0.6.0

Initial release on new documentation standards.