Alarms & Audit-Trail (Tutorial) teaches you to:
- Create alarm groups and items
- Configure alarm conditions
- Set up notifications
- Enable audit trail for FDA 21 CFR Part 11 compliance
Prerequisites:
In this page:
Create Alarm Groups
- Navigate to Alarms → Groups
- Edit the groups:
Critical | Warning |
---|---|
|
|
Define Alarm Items
- Go to Alarms → Items
- Create alarms:
High Temperature | Low Level |
---|---|
|
|
Configure Deviation Alarms
For rate-of-change monitoring:
- Name:
Pressure_Deviation
- Type: Deviation
- Tag:
Line_Pressure
- Setpoint Tag:
Pressure_Setpoint
- Deviation: ±10
- Time: 60 seconds
Audit Trail
- Go to Alarms → Audit Trail
- Enable logging:
- Login/Logout: Yes
- Tag Changes: Yes
- Alarm Acknowledgments: Yes
- Configuration Changes: Yes
Alarm Summary Display
- Go To Displays → List
- Create operator display
- Displays → New
- Add AlarmViewer control
- Configure:
- Show: Active alarms
- Columns: Time, Area, Message, Value
Test Alarms
- Start Runtime
- Open Alarms → Online
- Force tag values to trigger alarms
- Verify:
- Alarm appears in list
- Color coding correct
- Sound plays
- Email sent
Step-by-step guide to configure alarm groups, conditions, notifications, and audit trail for operational monitoring and FDA compliance.