The DF1 Serial driver implements communication with Rockwell Allen-Bradley devices using the DF1 Protocol (SLC Families and Micrologix) via Serial communication. It operates as a Master on serial networks. The communications blocks are dynamically created according to the pooling cycle defined on the Access Type for each Device Point.
Communication Driver Name: DF1 Serial
Current Version: 1.0
Implementation DLL: T.ProtocolDriver.DF1_Serial
Protocol: DF1
Interface: Serial
Max number of nodes: User defined
Supported Files:
Files | Read | Write | Data Type | Address Size |
---|---|---|---|---|
N | Yes | Yes | Word | 2 bytes |
B | Yes | Yes | Bit | 1 bit |
F | Yes | Yes | Single | 4 bytes |
O | Yes | Yes | Output | 1 bit |
I | Yes | Yes | Input | 1 bit |
CheckSum: It defines the checksum currently being used by the device, whether it’s CRC or BCC.
Set the fields according to your serial port configuration.
SlaveId: Set this field with the address of the slave device in the network.
The syntax for the DF1 Serial communication point is: <Files>:<Address>/Parameter
Where:
<Operand> indicates the memory area. The valid values are:
The operand also has a register value, except by I/O.
<Address> indicates the data address for the chosen file
<Parameter> indicates the specific bit of that address (which is a byte) (for the digital values)
E.g.:
The status of the driver execution can be observed through the diagnostic tools, which are:
• Trace window
• Property Watch
• Module Information
The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes.