Page Tree
Other Releases
The IndraControl communication driver implements communication with Bosch Rexroth IndraControl L20/L40 PLCs using a EtherNet/IP adapter.
Communication Driver Name: IndraControl
Implementation DLL: T.ProtocolDriver.IndraControl.dll
Manufacturer: Bosch Rexroth
Protocol: EtherNet/IP - Bosch
PLC Types Supported: Bosch Rexroth IndraControl L20/L40
Interface: TCP/IP
Supported Data:
Type | Read | Write | Data Type |
---|---|---|---|
EtherNet/IP Adapter Outputs | Yes | Yes | Byte Only |
EtherNet/IP Adapter Inputs | Yes | Byte Only |
None
Stations syntax: <IP>;<Port>;
Where :
Name | Channel | Primary Station |
---|---|---|
IndraControl | IndraControl | 192.168.200.105;44818 |
The syntax for the IndraControl communication points is: <%QB><Address> for Outputs and <%IB><Address> for inputs
E.g.: %QB1 (Type = Output, Address = 1)
TagName | Node | Address | DataType | AccessType |
---|---|---|---|---|
Output1 | IndraControl | %QB1 | Native | ReadWrite |
Output2 | IndraControl | %QB2 | Native | ReadWrite |
Output3 | IndraControl | %QB3 | Native | ReadWrite |
Output15 | IndraControl | %Q15 | Native | ReadWrite |
Input1 | IndraControl | %IB1 | Native | Read |
Input1 | IndraControl | %IB2 | Native | Read |
The status of the driver's execution can be observed through the diagnostic tools, which are:
• Trace window
• Property Watch
• Module Information
The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes.