Communication Driver Name: Facon
Implementation DLL: T.ProtocolDriver. Facon.dll
Protocol: FACON-PLC Communication Protocol
Interface: Serial or TCPIP
PLC types supported: Devices using the Facon Protocol
Manufacturer: FATEK AUTOMATION
PC Hardware requirements: COM Port or Ethernet board
The channel configuration options are system standard
DeviceID: The PLC Station Number. The valid values are 0 to 254, where 0 means the message is for all slave stations
For TCP/IP only:
The syntax for the Facon communication points is: <Operand><Address>
Where:
Operand | Read | Write | Bit Read | Bit Write | Data Types | Address Size |
---|---|---|---|---|---|---|
X Input discrete | Yes | Yes | Yes | Yes | Byte | 1 byte |
Y Output relay | Yes | Yes | Yes | Yes | Byte | 1 byte |
M Internal relay | Yes | Yes | Yes | Yes | Byte | 1 byte |
S Step relay | Yes | Yes | Yes | Yes | Byte | 1 byte |
T Timer discrete | Yes | Yes | Yes | Yes | Byte | 1 byte |
C Counter discrete | Yes | Yes | Yes | Yes | Byte | 1 byte |
TMR Timer register | Yes | Yes | Yes | Yes | Word | 2 bytes |
CTR Counter register | Yes | Yes | Yes | Yes | Word | 2 bytes |
HR Data register | Yes | Yes | Yes | Yes | Word | 2 bytes |
DR Data register | Yes | Yes | Yes | Yes | Word | 2 bytes |
Ex: M0 (Operand = M, Address = 0)
For bit read/write, use the Bit field in the Modifiers column under Edit > Devices > Points
The status of the driver's execution can be observed through the diagnostic tools, which are:
• Trace window
• Property Watch
• Module Information
The above tools indicate if the operations have succeeded or have failed. A status of 0 (zero) means communication is successful. Negative values indicate internal driver errors, and positive values indicate protocol error codes according to the Facon specification.