This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module.
Communication Driver Information | |
---|---|
Driver name | DHRIO |
Assembly Name | T.ProtocolDriver.DHRIO |
Assembly Version | 1.1.0.5 |
Available for Linux | False |
Devices supported | PLC5 or SLC500 devices using 1756-DHRIO (ControlLogix DHRIO Communication Module) in ControlLogix PLC. |
Manufacturer | Rockwell |
Protocol | DH+ network |
Interface | TCP/IP |
PC Requirements | Ethernet port |
Model: Select the PLC Model, 5 or 500.
Station syntax: <IP > ; <Port > ;<BackPlane>;<DHRIO Slot>;<DHRIO Channel>;<DH+ Node>
Where :
PrimaryStation = 192.168.1.101 ; 44818 ; 1 ; 2 ; A ; 0
The syntax for the AB Ethernet communication points is: <FileType><FileNumber>:<Address>[Parameter]
File | Read | Write | Bit Read | Bit Write | Data Type | Address size |
N Integer | Yes | Yes | Yes | Yes | Word | 2 bytes |
B Binary | Yes | Yes | Yes | Yes | Word | 2 bytes |
F FloatPoint | Yes | Yes | Yes | Yes | Single | 4 bytes |
O OutputLogical | Yes | Yes | Yes | Yes | Word | 2 bytes |
I InputLogical | Yes | - | Yes | - | Word | 2 bytes |
S Status | Yes | Yes | Yes | - | Word | 2 bytes |
T Timer (Model 500 only) | Yes | Yes | - | - | Word or Bit | 2 bytes or 1bit |
R Control (Model 500 only) | Yes | Yes | - | - | Word or Bit | 2 bytes or 1bit |
C Counter (Model 500 only) | Yes | Yes | - | - | Word or Bit | 2 bytes or 1bit |
FileNumber: File number related to the FileType.
Address: element address in configured File.
Parameter: Aditional parameter for Timer, Control and Counter.
Ex.: .Len, .Pre, .ACC, .EN, .TT, .DN, etc
Address = N7:10
DHRIO Revision History | |
---|---|
Version | Notes |
1.1.0.5 | Initial release on new documentation standards. |