Simatic/TI 505 and compatibles devices
On This Page:
SiemensTI505 driver implements communication with Simatic/TI 505 devices. For TCP/IP communication, the driver uses both CAMP and CAMP Packed Task Code messaging protocols for efficient data transfer.
Communication Driver Information | |
---|---|
Driver name | SimaticTI505 |
Assembly Name | T.ProtocolDriver.SimaticTI505 |
Assembly Version | 1.0.1.0 |
Available for Linux | False |
Devices supported | Simatic/TI 505 and compatibles devices |
Manufacturer | Siemens |
Protocol | CAMP and CAMP+Packed Task Code |
Interface | TCP/IP |
Multi-threading | User configurable. Default is five threads to each network node |
Max number of nodes | User defined |
PC Requirements | Ethernet port |
DataType | Variables | Format | Read | Write |
V | Memory | Short | Yes | Yes |
M | Memory | Short | Yes | Yes |
X | Discrete Input Packed | 16bits | Yes | Yes |
Y | Discrete Output Packed | 16bits | Yes | Yes |
C | Control Register Packed | 16bits | Yes | Yes |
WX | Word Input | Short | Yes | Yes |
WY | Word Output | Short | Yes | Yes |
TCP | Time/Counter Preset | Short | Yes | Yes |
TCC | Time/Counter Current | Short | Yes | Yes |
DSP | Drum Step Preset | Short | Yes | Yes |
DSC | Drum Step Current | Short | Yes | Yes |
DCP | Drum Count Preset | Short | Yes | Yes |
STW | System Status Word | 16bits | Yes | - |
DCC | Drum Current Count | 32bits | Yes | - |
The driver supports the following protocols:
TCP/IP channels:
TCP/IP channels:
Where :
E.g.: 192.168.1.101 ;1505
The syntax for the SiemensTI505 communication points is: <DataType><Address>
Where:
DataType | Variables |
---|---|
V | Memory |
M | Memory |
X | Discrete Input Packed |
Y | Discrete Output Packed |
C | Control Register Packed |
WX | Word Input |
WY | Word Output |
TCP | Time/Counter Preset |
TCC | Time/Counter Current |
DSP | Drum Step Preset |
DSC | Drum Step Current |
DCP | Drum Count Preset |
STW | System Status Word |
DCC | Drum Current Count |
For more information about the valid data type, see the Supported Operands table aforementioned.
E.g.: V100 (DataType = V, Address = 100)
Select Single DataType with WordSwap equal true (Modifiers column) for float-point format. |
SimaticTI505 Revision History | |
---|---|
Version | Notes |
1.0.1.0 | Initial release on new documentation standards. |