or: Control-Room Operators, Maintenance Techs
Focus: Runtime monitoring & diagnostics
Operators and maintenance staff responsible for day-to-day running of FrameworX solutions: monitoring health, responding to alarms, reviewing trends/reports, performing basic diagnostics, and executing shift handovers. (See AlarmViewer, TrendChart, Runtime System Monitor, Diagnostics Tools, Audit Trail, Security/RuntimeUsers, ReportViewer in the docs.)
Monitor system health and data flows in real time
Respond to alarms consistently and document actions
Use trends, annotations, and reports to investigate issues
Perform first-line diagnostics on comms, clients, and historian
Execute shift handover & maintain audit/compliance records
Apply runtime security best practices and least-privilege access
Your Role | Primary Focus | Essential Pages | Advanced Topics | |
---|---|---|---|---|
System Integrator | Full platform | Platform Overview | Solution Lifecycle | Security & Operations |
Control Engineer | Field connectivity | Solution Lifecycle | P2: Process Modules | Alarms Module |
HMI Developer | User interfaces | Designer | Displays Module | Security Module |
IT Administrator | Deployment | Architecture | Runtime | Product Editions |
Project Manager | Capabilities | Platform Overview | Product Editions | Technology Foundation |
Topics
SmartClient / Web Client basics: login, navigation, bookmarks, user settings
Display layouts, symbols, and operator-level interactions (buttons, popups, dashboards)
Report viewing (ReportViewer) and quick exports
Exercise:
Log in with an operator role; open the overview display; bookmark three critical pages; run a daily production report; export to CSV/PDF.
Quick-Check Card (post on the wall)
Check | How |
---|---|
Server/Runtime status | Runtime System Monitor page |
Client connectivity | Web Client Connection Checklist |
Time sync | Verify NTP source in system notes |
Topics
Alarm philosophy recap (states, severity, shelving/ack, notes)
AlarmViewer usage: filters, areas, duration field, history drill-down
Notifications and escalation overview (email/SMS policies)
Playbook (baseline)
Identify alarm → confirm area & equipment
Acknowledge with note (reason/action)
Execute SOP steps; verify return-to-normal
Annotate trend; create follow-up task if recurrence
Shift log entry + handover
Exercise:
Run three alarm scenarios (process limit, device offline, bad quality). Capture notes, annotations, and outcome.
Topics
TrendChart basics: pens, cursors, time windows, annotations, saving views
Historian concepts: tags, retention, exporting to CSV; Historian Monitor
Daily/weekly reports for production and alarm KPIs
Lab:
Create a saved trend view for a critical asset; add two annotations linked to an alarm; export a 24-hour CSV; attach to a shift report.
Topics
Runtime System Monitor: services, CPU/RAM, queue/backlog indicators
Device/connection monitors; quick comms checks (Ping/SNMP)
Diagnostics Tools & common issues (HTTPS/SSL, client download blocks)
Diagnostics Matrix (use on incidents)
Symptom | First Checks | Likely Fix |
---|---|---|
Tag stale/bad | Device node status; channel link | Re-establish comms; check routing/firewall |
Client slow | Display point count; network latency | Use smaller views; verify bandwidth |
Trend gap | Historian service & storage | Confirm service; free disk space |
Login fails | AD/LDAP reachability; role | Verify directory & permissions |
Topics
Audit Trail usage during operations (who did what/when)
RuntimeUsers, permissions, and least-privilege access
Shift handover notes and attachments; report bundles
Deliverables
Shift Handover Template (what happened, alarms of concern, pending work orders)
Operator SOP binder: alarm response, comms check, report schedule
Topics
Using trends/reports to spot drift; simple KPIs per asset
Creating “watch” views; thresholds for early warnings
Optional: link to CMMS via datasets/exports (process outline)
Exercise:
Define three early-warning indicators and a weekly review report.
Topics
Roles/permissions for operators vs. maintenance; temporary elevation process
AD/LDAP integration overview; policy for password/account hygiene
Exercise:
Review current roles; remove excess privileges; test operator sign-in & access to required pages only.
Topics
Display optimization habits (lazy loading, fewer live points per view)
Historian query hygiene (time windows, pen counts)
Client/network basics (when to call IT vs. fix locally)
Lab:
Split an overloaded display into two; measure load improvement; document best practice.
Topics
Hot-standby / redundancy overview; operator steps during failover
Backup/restore awareness; where to find runbooks
Notification test: confirm emails/SMS reach the right on-call list
Drill:
Simulate primary outage; execute client reconnection & verification checklist; record times.
Operator Practical (90 min)
Handle a 3-alarm sequence with notes, annotations, and report
Diagnose a comms outage using monitors/diagnostics
Complete shift handover with audit proof
Certification: FrameworX Operations Specialist
Format: scenario practical + short quiz; validity 2 years; CE via annual drill.
Alarm Severity → Response Time
Severity | Target Ack | Target Resolve |
---|---|---|
Critical | ≤ 1 min | ≤ 15 min |
High | ≤ 5 min | ≤ 60 min |
Medium | ≤ 15 min | Shift |
Low | ≤ 60 min | As scheduled |
Daily Runtime Checklist
Review Runtime System Monitor (CPU/RAM/queues)
Scan AlarmViewer filters for standing alarms
Verify historian ingestion & free disk space
Run daily production/alarm report and archive
Note issues in shift log; prep handover
Shift Handover Essentials
Top 5 alarms & status, open actions
Equipment on watch, current trends attached
Any client/network anomalies observed
Maintenance requests raised & references
Sign-off with Audit Trail entry
AlarmViewer Control & Alarm Areas/Module pages (operations UI)
TrendChart Control & Trend Settings (trending & annotations)
Runtime System Monitor & Diagnostics Tools / Common Issues
Audit Trail; Security RuntimeUsers / AD-LDAP (accountability & access)
ReportViewer Control & Reports Module (daily/weekly reports)
Notes: Page labels above map to the FrameworX 10.1 doc sections (e.g., AlarmViewer on p.11; TrendChart on p.10; Runtime System Monitor & Deployment on p.10; Diagnostics/Common Issues on p.11; Audit Trail in Alarms Module on p.8; Security/RuntimeUsers on p.9; ReportViewer on p.11).